Section 3 — Operation

Liquid-cooled 30 kW Generators

The system ready LED will be OFF when the switch is in the manual or OFF positions.

Figure 3.2 — Engine Governor Adjustment

The system ready LED is also used to indicate the presence of utility sensing at the PCB when the switch is either in the AUTO or MANUAL modes. The LED will flash at the rate of 1/2 second on, 1/2 second off if the utility sensing level is below the transfer back threshold.

This secondary function is only available with dip switch two in the OFF position (standard ATS appli- cation).

3.3MANUAL TRANSFER AND

START-UP

To transfer electrical loads to the Standby (EMERGENCY) power source side and start the engine manually, refer to the Owner’s Manual of the particular transfer switch.

3.4ENGINE GOVERNOR

LED1

2

U7

C4

C30

R25

R49

U1

.REV

E4906 PCB#

DIFFERENTIAL STABILITY

 

 

 

R44

 

C9

C27

Q2

 

 

 

 

 

 

J2

 

 

 

 

C26

 

 

 

 

D10

 

 

 

 

C21

 

C2

 

 

 

 

 

 

 

 

 

 

 

 

 

RL1

 

RL2

 

R1

 

 

 

 

R48

 

 

 

 

D17

 

 

 

 

 

 

 

J1

 

L3

 

 

 

 

 

 

 

D19

 

DIP SWITCH

 

4

UNUSED

POSITION 1

POSITION 2

3

50/60 HZ

GTS/ATS Select

 

 

2

GTS/ATS

ON = 50 HZ

ON = GTS

OFF = 60 HZ

OFF = ATS (standard mode)

1

50/60 HZ

 

 

ADJUSTMENTS

Engine speed governing is also controlled by the engine control board. Connector J2 on the engine control board interfaces with a governor driver mod- ule and the Bosch throttle body. The engine gover- nor has been set by the factory during final testing of the generator and, in most cases, should not be adjusted.

If, however, adjustments are necessary, or a new engine control board is installed in the generator, the following procedure should be followed (Figure 3.2):

1.Set all three potentiometers (pots) fully counter- clockwise.

2.Under no load condition, increase the GAIN pot as much as possible without causing instability.

3.Apply 1/4, 1/2, 3/4 and full load to the unit. Decrease the GAIN pot if there is instability at any load point.

4.Under full load condition, increase the stability pot until the unit returns to 60 Hertz (or 50 Hertz in 50 Hertz applications).

5.Reduce load to 3/4, 1/2, 1/4 and no load. Decrease the stability pot if there is instability at any load point.

6.Adjust differential pot to make the recovery to load changes even faster and minimize load change undershoot and overshoot. If it is set too high it may introduce oscillations at some load. It can be set to zero (full CCW) if a small amount causes oscillations at some load.

14

3.5RETRANSFER AND SHUTDOWN

When utility power source voltage has been restored, electrical loads may be transferred back to that source and the generator can be shut down as fol- lows:

Verify that UTILITY power supply voltage to the transfer switch has been positively turned OFF, using whatever means provided (such as utility main line circuit breaker).

Set the generator’s main circuit breaker to its OFF or OPEN position.

Let the generator engine run at no-load for a few minutes, to stabilize internal unit temperatures.

On the generator console, set the AUTO/OFF/ MANUAL switch to OFF. Wait for engine to come to a complete stop.

For transfer to utility position, refer to the Owner’s Manual of the particular transfer switch.

Turn on the UTILITY power supply to the transfer switch, using whatever means provided (such as a utility main line circuit breaker). The UTILITY power source now powers the loads.

3.6AUTOMATIC OPERATION

To set the system for fully automatic operation, pro- ceed as follows:

Check that load circuits are connected to the utility power supply.

Set the AUTO/OFF/MANUAL switch to its AUTO position.

Set the generator main circuit breaker to its ON or CLOSED position.

Image 16
Contents Liquid-cooled, Prepackaged Standby Generators Authorized Service Dealer Location ‹ Operation and Maintenance‹ HOW to Obtain Service IntroductionTable of Contents  Warning   Electrical Hazards  Transfer Switch GeneratorAutomatic System Operation Generator AC Connection Systems‹ 1.7.2 High Coolant Temperature Switch ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.3 LOW Coolant Level Switch LOW OIL Presure Switch LOW Coolant Level SwitchUnpacking Lifting the GeneratorSpecifications Reconfiguring the Fuel System‹ 1.10.1 Generator Specifications ‹ 1.10.2 Engine SpecificationsTorque Specifications Standby Generator InstallationBefore Installation Engine OIL RecommendationsBasic Standby Electric System Generator Mounting Support‹ 2.1.2 Other Published Standards Transfer Switch Signal Connections Emergency Circuit Isolation MethodTotal Circuit Isolation Method Grounding the GeneratorPreparation Before START-UP Battery Installation‹ 2.9.2 GTS-TYPE ATS Using AN Engineered GTS Transfer Switch ‹ 3.2.1 AUTO/OFF/MANUAL Switch ‹ 3.2.2 Fault Indicator LED‹ 3.2.5 SET Exercise Time Switch Control Console ComponentsAdjustments Manual Transfer START-UP Engine GovernorRetransfer and Shutdown Automatic OperationWeekly Exercise Cycle Cooling SystemOverload Protection for Engine DC Electrical System Checking Fluid Levels‹ 4.5.11 Changing the Engine AIR Cleaner ‹ 4.5.8 Check FAN Belt‹ 4.5.9 Inspect Engine Governor ‹ 4.5.10 Changing Engine OILMiscellaneous Maintenance ‹ 4.6.3 Battery Maintenance‹ 4.6.1 Cleaning the Generator ‹ 4.5.13 Coolant Change‹ 4.6.4 Battery Replacement ‹ Periodic Replacement PartsScheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionLiquid-cooled 30 kW Generators Installation Diagram Transfer Switch AUTO/OFF/MANUAL SwitchSET Exerciser Switch Size AWGOtherwise Noted AS Shown BATIgnition Coil On PCBSWITCH, SET Exerciser SWITCH, AUTO/OFF/MANUALDPE 12V Battery RED ALTDEG Starter Motor GOVEngine Foot Boot Battery Cable Battery Post Cover BaclkBattery Post Cover RED + Hold Down BatteryTo a To B Plcs Assy Wire 14AWG 7.5 #0 GRN/YEL Intake Duct HSBDuct Discharge RH Front Duct Discharge LH FrontPage Assy 2A 12V UL Battery Control BOX HSBDecal AVR Cover Cover Front Panel HSBCooled 30 kW Drawing No Exploded Wire SET 3.0L Ford not Not SHOWN-USED to Hold OIL Drain AssemblyCoil Ignition 3.0L Ford Bracket DC ALT 3.0L FordFrame Tank Coolant Recovery Radiator R-IN,L-OUTVenturi 3.0L Ford HSB Side Support Radiator HSBTo B Weldment Mounting Base Flange Fuel InletAssy Regulator 3.0L NG or LPV Washer Flat 5/16 ZincLocktight Rotor 390 15KW 1P Direct HSB 2.5L Ford Rotor 390 20KW 1P Direct HSB 2.5L FordRotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 39030AD1 HSB TecumExhaust Flange 2 Pipe Pipe Muffler OUTWasher Lock 3/8 SS Gasket Exhaust RingPlate AIR Cleaner Adapter Element AIR CleanerCover AIR Cleaner Adapter Carburetor W/PVC ConnWarranty Schedule