Generac Power Systems 2.4L owner manual Specifications

Page 10

Standby Generator Sets

Specifications

SPECIFICATIONS

‹ GENERATOR

Type

Synchronous

Rotor Insulation

Class F

Stator Insulation

Class H

Total Harmonic Distortion

<5%

Telephone Interference Factor (TIF)

< 50

Alternator Output Leads 3-phase

6-wire

Bearings

Sealed Ball

Coupling

Flexible Disc

Load Capacity (Standby Rating)

25kW*

*NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate with natural gas.

Excitation System

 

Direct

Generator Output Voltage/kW - 60 Hz

kW

Amp

CB Size

120/240V, 1-phase, 1.0 pf

25

104

125

120/208V, 3-phase, 0.8 pf

25

87

100

277/480V, 3-phase, 0.8 pf

25

38

40

Generator Locked Rotor KVA Available @ Voltage Dip of 35%

Single-phase

 

50 KVA

208V, 3-phase

 

70 KVA

480V, 3-phase

 

70 KVA

‹ ENGINE

Make

Generac

Model

In Line

Cylinders and Arrangement

4

Displacement

2.4 Liter

Bore

3.41 in.

Stroke

3.94 in.

Compression Ratio

8.5-to-1

Air Intake System

Naturally Aspirated

Valve Seats

Hardened

Lifter Type

Hydraulic

Engine Parameters

 

Rated Synchronous RPM

60 Hz, 1800

HP at rated kW

60 Hz, 40

Exhaust System

 

Exhaust Flow at Rated Output 60 Hz

130 cfm

Exhaust Temperature at Rated Output

900° F

Combustion Air Requirements (Natural Gas)

Flow at rated power, 60 Hz

70 cfm

Governor

 

Type

Electronic

Frequency Regulation

Isochronous

Steady State Regulation

± 0.25%

Engine Lubrication System

 

Type of Oil Pump

Gear

Oil Filter

Full Flow Spin-on, Cartridge

Crankcase Oil Capacity

4 U.S. qts.

‹ COOLING SYSTEM

Type

Pressurized Closed Recovery

Water Pump

Belt Driven

Fan Speed

1000 rpm

Fan Diameter

22 inches

Fan Mode

Puller

Air Flow (inlet air...........................................................including alternator and

1600 ft3/min.

combustion air)

 

Coolant Capacity

(3.0 U.S. gal.)

Heat Rejection to Coolant

106,900 Btu/h

Maximum Operating Air Temp. on Radiator

60° C (150° F)

Maximum Ambient Temperature

50° C (140° F)

‹FUEL SYSTEM

Type of Fuel

.........................................

Natural Gas, Propane Vapor

Carburetor

 

 

Down Draft

Secondary Fuel Regulator

 

Standard

Fuel Shut-off Solenoid

 

Standard

Operating Fuel Pressure

5 in. - 14 in. Water Column

Fuel Consumption - ft3/hr (Natural Gas/LPV)

Exercise

25%

50%

75%

100%

Cycle

Load

Load

Load

Load

42/16

107/41

204/77

293/111

375/142

‹ELECTRICAL SYSTEM

Battery Charge Alternator

12V, 30 Amp

Static Battery Charger

2 Amp

Recommended Battery

Group 26, 525CCA

System Voltage

12 Volts

Voltage Regulator

 

Type

Electronic

Sensing

Single-phase

Regulation

± 1%

Features

V/F Adjustable, Adjustable

 

Voltage and Gain LED Indicators

Power Adjustment for Ambient Conditions

Temperature Deration

 

3% for every 10° C above °C

25

1.65% for every 10° above °F

77

Altitude Deration

 

1% for every 100 m above m

183

3% for every 1000 ft. above ft

600

Controller

R-200

6-1

05/07 A .Rev GenSpec031

Image 10
Contents 25kW Models Standby Generator Sets Table of Contents  Warning   Electrical Hazards  Introduction ‹ Operation and Maintenance‹ HOW to Obtain Service ‹ Read this Manual ThoroughlyIdentification Record ‹ Data Label Engine OIL Recommendations Equipment Description Coolant Recommendations Engine Protective Devices ‹ Natural GAS Fuel System Fuel System‹ Fuel Requirements ‹ LP Fuel SystemSpecifications ‹ Reconfiguring the Fuel System ‹ Cold Weather KIT‹ 3-PHASE Alternators Alternator Power Winding Connections‹ FOUR-LEAD, SINGLE-PHASE Stator Generator AC Lead ConnectionsPreparation Before START-UP InstallationInitial Inspection for Genset Startup START-UP Checklist ‹ Preparation for START-UP‹ Engine START-UP and Transfer Operating Unit with Manual Transfer SwitchGenerator Control Operation ‹ Retransfer and ShutdownCooling System Maintenance Performed by Service FacilitiesChecking Fluid Levels Maintenance Owner Operator can Perform ‹ Changing Engine OIL ‹ Changing the Engine AIR Cleaner ‹ Coolant Change‹ Spark Plugs Miscellaneous Maintenance Repair PartsService Schedule KW 150 KW Standby GAS Engine Driven Generator SetsMaintenance Level 11-3 11-4 Troubleshooting Guide Problem Cause CorrectionStandby Generator Sets Standby Generator Sets Page PAN CB Conn BOX Page UL Circuit Breaker QJ-2P Page Assy STR 390 25AD1 CPL Page Components Included in 0G2283D Page Weldment Frame 2.4L C2 Page Battery Tray C1 CPL Page Gasket Bosch 32 Page Engine 2.4L Mitsubishi 4G64 Page Weldment Radiator Support 2.4L Page Flange Fuel Inlet Page Rear Wrap C2 CPL Page Exhaust Elbow 2 1/4 OD 2 1/2OD Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page C2 Units 04/07 a .Rev BackPg001