Generac Power Systems 2.4L owner manual Maintenance Owner Operator can Perform

Page 17

Standby Generator Sets

Maintenance

Remove oil dipstick and wipe dry with a clean, lint- free cloth.

Install oil dipstick, then remove again.

Oil should be between FULL and ADD marks.

If oil level is below the dipstick ADD mark, remove oil fill cap-. Add the recommended oil to bring oil level up to the FULL mark. DO NOT FILL ABOVE THE “FULL” MARK. See “Engine Oil Recommen- dations” for recommended oils.

‹BATTERY FLUID

Check battery electrolyte fluid based on the Maintenance Schedule. Fluid should cover separa- tors in all battery cells. If fluid level is low, add dis- tilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.

‹INSPECT COOLING SYSTEM

Inspect engine cooling system. See “Maintenance Schedule”.

Check hoses for damage, deterioration, leaks, etc. Correct any discrepancies found.

Check hose clamps for tightness.

‹CHECK ENGINE COOLANT LEVEL

See “Checking Fluid Levels”.

‹PERFORM VISUAL INSPECTION

Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.

‹ENGINE COOLANT

Check coolant level in coolant recovery bottle. See Specifications.

Add recommended coolant mixture as necessary.

Periodically remove radiator pressure cap (only when engine has cooled down) to make sure the coolant recovery system is functioning properly. Coolant should be at bottom of radiator filler neck. If coolant level is low, inspect gasket in radiator pressure cap. Replace cap, if necessary. To have pressure cap tested, contact a Service Dealer. Inspect cooling system and coolant recovery sys- tem for leaks.

MAINTENANCE OWNER/

OPERATOR CAN PERFORM

‹CHECK ENGINE OIL LEVEL

Refer to “Checking Fluid Levels”.

‹CHECK BATTERY

See “Checking Fluid Levels”.

Check battery cables for condition, tightness, cor- rosion or damage. Clean, tighten or replace as necessary.

‹EXERCISE SYSTEM

Start the generator engine at least once every seven days and let it run at least 20 minutes. For more detailed exercise information, see the respective sec- tions in the Control Panel Technical Manual that is supplied with the unit.

‹INSPECT EXHAUST SYSTEM

Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.

‹CHECK FAN BELT

Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defec- tive belt.

Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 5/8 of an inch. Adjust belt tension as required.

‹INSPECT ENGINE GOVERNOR

Visually inspect electronic governor.

DANGER

Do not attempt to adjust the governor. Only qualified service facilities should adjust the governor. Excessively high operating speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may shorten engine life. Correct rated frequency and voltage are supplied only at the proper governed speed. Some connected electrical load devices may be damaged by incor- rect frequency and/or voltage. Only qualified service technicians should adjust the governed speed.

06/07 D .Rev Maint012

10-2

Image 17
Contents 25kW Models Standby Generator Sets Table of Contents  Warning   Electrical Hazards  ‹ HOW to Obtain Service ‹ Operation and MaintenanceIntroduction ‹ Read this Manual Thoroughly‹ Data Label Identification RecordCoolant Recommendations Equipment DescriptionEngine OIL Recommendations Engine Protective Devices ‹ Fuel Requirements Fuel System‹ Natural GAS Fuel System ‹ LP Fuel SystemSpecifications ‹ Cold Weather KIT ‹ Reconfiguring the Fuel System‹ FOUR-LEAD, SINGLE-PHASE Stator Alternator Power Winding Connections‹ 3-PHASE Alternators Generator AC Lead ConnectionsInitial Inspection for Genset Startup InstallationPreparation Before START-UP ‹ Preparation for START-UP START-UP ChecklistGenerator Control Operation Operating Unit with Manual Transfer Switch‹ Engine START-UP and Transfer ‹ Retransfer and ShutdownChecking Fluid Levels Maintenance Performed by Service FacilitiesCooling System Maintenance Owner Operator can Perform ‹ Spark Plugs ‹ Changing the Engine AIR Cleaner ‹ Coolant Change‹ Changing Engine OIL Repair Parts Miscellaneous MaintenanceKW 150 KW Standby GAS Engine Driven Generator Sets Service ScheduleMaintenance Level 11-3 11-4 Problem Cause Correction Troubleshooting GuideStandby Generator Sets Standby Generator Sets Page PAN CB Conn BOX Page UL Circuit Breaker QJ-2P Page Assy STR 390 25AD1 CPL Page Components Included in 0G2283D Page Weldment Frame 2.4L C2 Page Battery Tray C1 CPL Page Gasket Bosch 32 Page Engine 2.4L Mitsubishi 4G64 Page Weldment Radiator Support 2.4L Page Flange Fuel Inlet Page Rear Wrap C2 CPL Page Exhaust Elbow 2 1/4 OD 2 1/2OD Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page C2 Units 04/07 a .Rev BackPg001

2.4L specifications

Generac Power Systems has established itself as a leading provider of energy solutions, and its 2.4L engine is a testimony to their commitment to innovation and reliability. This engine is designed for portable and standby generators, delivering exceptional performance and efficiency.

One of the standout features of the Generac 2.4L engine is its robust design, optimized for both heavy-duty use and demanding applications. The engineering focus ensures that the engine can withstand various environmental conditions while maintaining optimal operation. Additionally, its compact size makes it versatile for various generator models, making it a favored choice among manufacturers and users.

The 2.4L engine incorporates advanced technologies that enhance performance and fuel efficiency. One notable technology is the Electronic Fuel Injection (EFI) system. Unlike traditional carbureted engines, the EFI system provides precise fuel management, improving fuel efficiency and reducing emissions. This means users can expect longer run times on a single tank of fuel, a crucial advantage for those requiring power during outages or remote operation.

Furthermore, the Generac 2.4L engine is equipped with a state-of-the-art cooling system that maintains optimal operating temperatures even under heavy loads. This safeguard helps prevent overheating, thus extending the engine's longevity and reliability. The engine's low oil pressure shutdown feature adds another layer of protection by automatically shutting down the engine if oil pressure drops below a safe threshold.

Noise reduction is another priority for Generac, and the 2.4L engine reflects this commitment. With an integrated muffler and sound suppression features, the engine operates quietly without sacrificing power output. This is particularly beneficial for residential areas or environments where noise may be a concern.

In terms of maintenance, the Generac 2.4L engine requires minimal upkeep. Its design includes easily accessible components, allowing for straightforward maintenance routines. Regular oil changes and filter replacements ensure that the engine continues to perform at its best over time, providing users with peace of mind.

Overall, the Generac Power Systems 2.4L engine combines innovative features, advanced technologies, and reliable performance, making it an attractive choice for those in need of dependable power solutions. Whether for home backup or professional use, this engine exemplifies Generac's dedication to quality and user satisfaction.