Generac Power Systems 2.4L owner manual Installation, Preparation Before START-UP

Page 13

Standby Generator Sets

Installation

INSTALLATION

‹PRIOR TO INITIAL START-UP

Refer to the separate “Installation Guide” supplied with the unit.

PREPARATION BEFORE START-UP

The instructions in this section assume that the standby generator has been properly installed, ser- viced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules”, as well as all other safety information in this manual, before attempting to operate this (and related) equipment.

Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service intervals, please refer to the “Maintenance” section and the “Service Schedule”.

‹TRANSFER SWITCH

If this generator is used to supply power to any elec- trical system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed. The transfer switch prevents elec- trical backfeed between two different electrical sys- tems. (For additional information, see the applicable transfer switch manual for this unit.) The transfer switch, as well as the generator and other standby components, must be properly located and mounted in strict compliance with applicable codes, standards and regulations.

‹FUEL SYSTEM

Make sure the fuel supply system to the generator (a) delivers the correct fuel at the correct pressure and (b) is properly purged and leak tested according to code. No fuel leakage is permitted. See “Specifications” for more information.

‹GENERATOR SET LUBRICATION

Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See “Specifications” and “Engine Oil Recommendations”.

NOTE:

This engine is shipped from the manufacturer with “break-in” oil. This oil should be changed after 30 hours of operation.

Prior to initially starting the generator, it must be properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quantities of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure.

‹ENGINE COOLANT

Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See “Specifications” and “Coolant” sections.

‹BELT TENSION

Check-the engine-fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approximately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8- inch (10 to 16 mm).

‹ELECTRICAL SYSTEM

Make sure the generator is properly connected to an approved earth ground.

Make sure the generator battery is fully charged, properly installed and interconnected, and ready for use.

NOTE:

Battery charger must be connected to 120 VAC, 15 amp circuit to operate.

Check to ensure that there are no loose electrical con- nections. Restrain any loose wires to keep them clear of any moving generator set components.

INITIAL INSPECTION FOR GENSET STARTUP

Inspect for the following.

Freight Damage.

Manuals present.

Fluid Levels (Oil, coolant, battery, Gear Drive).

Correct fuel piping.

Adequate air flow, clearances and ventilation per installation drawings and applicable codes.

Correct AC and DC wire size, connections and grounding. Control and communication wiring to/ from the transfer switch must be run in a separate conduit from the AC power leads.

8-1

01/07 C .Rev Install002

Image 13
Contents 25kW Models Standby Generator Sets Table of Contents  Warning   Electrical Hazards  ‹ HOW to Obtain Service ‹ Operation and MaintenanceIntroduction ‹ Read this Manual Thoroughly‹ Data Label Identification RecordEngine OIL Recommendations Equipment DescriptionCoolant Recommendations Engine Protective Devices ‹ Fuel Requirements Fuel System‹ Natural GAS Fuel System ‹ LP Fuel SystemSpecifications ‹ Cold Weather KIT ‹ Reconfiguring the Fuel System‹ FOUR-LEAD, SINGLE-PHASE Stator Alternator Power Winding Connections‹ 3-PHASE Alternators Generator AC Lead ConnectionsPreparation Before START-UP InstallationInitial Inspection for Genset Startup ‹ Preparation for START-UP START-UP ChecklistGenerator Control Operation Operating Unit with Manual Transfer Switch‹ Engine START-UP and Transfer ‹ Retransfer and ShutdownCooling System Maintenance Performed by Service FacilitiesChecking Fluid Levels Maintenance Owner Operator can Perform ‹ Changing Engine OIL ‹ Changing the Engine AIR Cleaner ‹ Coolant Change‹ Spark Plugs Repair Parts Miscellaneous MaintenanceKW 150 KW Standby GAS Engine Driven Generator Sets Service ScheduleMaintenance Level 11-3 11-4 Problem Cause Correction Troubleshooting GuideStandby Generator Sets Standby Generator Sets Page PAN CB Conn BOX Page UL Circuit Breaker QJ-2P Page Assy STR 390 25AD1 CPL Page Components Included in 0G2283D Page Weldment Frame 2.4L C2 Page Battery Tray C1 CPL Page Gasket Bosch 32 Page Engine 2.4L Mitsubishi 4G64 Page Weldment Radiator Support 2.4L Page Flange Fuel Inlet Page Rear Wrap C2 CPL Page Exhaust Elbow 2 1/4 OD 2 1/2OD Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page C2 Units 04/07 a .Rev BackPg001

2.4L specifications

Generac Power Systems has established itself as a leading provider of energy solutions, and its 2.4L engine is a testimony to their commitment to innovation and reliability. This engine is designed for portable and standby generators, delivering exceptional performance and efficiency.

One of the standout features of the Generac 2.4L engine is its robust design, optimized for both heavy-duty use and demanding applications. The engineering focus ensures that the engine can withstand various environmental conditions while maintaining optimal operation. Additionally, its compact size makes it versatile for various generator models, making it a favored choice among manufacturers and users.

The 2.4L engine incorporates advanced technologies that enhance performance and fuel efficiency. One notable technology is the Electronic Fuel Injection (EFI) system. Unlike traditional carbureted engines, the EFI system provides precise fuel management, improving fuel efficiency and reducing emissions. This means users can expect longer run times on a single tank of fuel, a crucial advantage for those requiring power during outages or remote operation.

Furthermore, the Generac 2.4L engine is equipped with a state-of-the-art cooling system that maintains optimal operating temperatures even under heavy loads. This safeguard helps prevent overheating, thus extending the engine's longevity and reliability. The engine's low oil pressure shutdown feature adds another layer of protection by automatically shutting down the engine if oil pressure drops below a safe threshold.

Noise reduction is another priority for Generac, and the 2.4L engine reflects this commitment. With an integrated muffler and sound suppression features, the engine operates quietly without sacrificing power output. This is particularly beneficial for residential areas or environments where noise may be a concern.

In terms of maintenance, the Generac 2.4L engine requires minimal upkeep. Its design includes easily accessible components, allowing for straightforward maintenance routines. Regular oil changes and filter replacements ensure that the engine continues to perform at its best over time, providing users with peace of mind.

Overall, the Generac Power Systems 2.4L engine combines innovative features, advanced technologies, and reliable performance, making it an attractive choice for those in need of dependable power solutions. Whether for home backup or professional use, this engine exemplifies Generac's dedication to quality and user satisfaction.