Generac Power Systems 2.4L Generator Control Operation, ‹ Engine START-UP and Transfer

Page 15

Standby Generator Sets

Operation

GENERATOR CONTROL AND

OPERATION

Refer to the appropriate control panel operator’s manual for this unit.

OPERATING UNIT WITH MANUAL TRANSFER SWITCH

If the generator was installed in conjunction with a transfer switch capable of manual operation only, the following procedure applies. A manually operated transfer switch is one that will not provide automatic start-up and does not include an intelligence circuit.

‹ENGINE START-UP AND TRANSFER

For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.

DANGER

The Maintenance Disconnect Switch and the AUTO/OFF/MANUAL switches (if so equipped) must be set properly, or the generator will crank and start as soon as the utility power to the transfer switch is turned off. Refer to applicable control panel and transfer switch manuals for more information.

Do not proceed until certain that utility source voltage is available to the transfer switch and the transfer switch main contacts are set to

UTILITY.

Do not attempt manual operation until all power supplies to the transfer switch have been posi- tively turned off, or extremely dangerous - pos- sibly lethal - electrical shock will result.

Transfer switch enclosure doors should be kept closed and locked. Only authorized personnel should be allowed access to the transfer switch interior. Extremely high and dangerous voltages are present in the transfer switch.

In order to transfer load from the utility source to the generator, follow these directions:

Turn OFF or disconnect the utility power circuit to the transfer switch, using the means provided (such as the utility source main line circuit break- er).

Set the transfer handle to its UTILITY (NORMAL) position with load circuits connected to the utility power supply.

Set the standby generator’s main line circuit break- er to its OFF (or OPEN) position.

Start the generator.

Do not crank the engine continuously for longer than 30 seconds, or the heat may

damage the starter motor.

Let engine stabilize and warm up.

Check all applicable instrument and gauge read- ings. When certain that all readings are correct, move the transfer switch manual handle to its STANDBY (GENERATOR) position, i.e., load cir- cuits supplied by the generator.

Set the standby generator’s main line circuit break- er to its ON (or CLOSED) position.

Load circuits are now powered by the standby generator.

‹RETRANSFER AND SHUTDOWN

For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.

To transfer the load back to the utility power source and shut down the generator, follow these direc- tions:

Set the standby generator’s main line circuit break- er to its OFF (or OPEN) position.

Manually move the transfer switch handle to its UTILITY (NORMAL) position, i.e., load circuits connected to the utility.

Turn ON the utility power supply to the transfer switch, using the means provided (such as the util- ity power source main line circuit breaker).

Let the generator run at no-load for a few minutes to stabilize internal temperatures.

Shut down the generator.

OPERATING UNIT WITH AUTOMATIC TRANSFER SWITCH

If the generator has been installed with an automatic transfer switch, such as an RTS, HTS, or GTS-type transfer switch, the engine may be started and stopped automatically or manually.

NOTE:

Refer to the applicable manual for your trans- fer switch and to “Transfer Switch Start Signal Connections”. In addition, please note the dangers under “Engine Start-up and Transfer.”

9-1

08/05

0 .Rev Oper001

Image 15
Contents 25kW Models Standby Generator Sets Table of Contents  Warning   Electrical Hazards  ‹ Read this Manual Thoroughly ‹ Operation and Maintenance‹ HOW to Obtain Service Introduction‹ Data Label Identification RecordEquipment Description Engine OIL RecommendationsCoolant Recommendations Engine Protective Devices ‹ LP Fuel System Fuel System‹ Fuel Requirements ‹ Natural GAS Fuel SystemSpecifications ‹ Cold Weather KIT ‹ Reconfiguring the Fuel SystemGenerator AC Lead Connections Alternator Power Winding Connections‹ FOUR-LEAD, SINGLE-PHASE Stator ‹ 3-PHASE AlternatorsInstallation Preparation Before START-UPInitial Inspection for Genset Startup ‹ Preparation for START-UP START-UP Checklist‹ Retransfer and Shutdown Operating Unit with Manual Transfer SwitchGenerator Control Operation ‹ Engine START-UP and TransferMaintenance Performed by Service Facilities Cooling SystemChecking Fluid Levels Maintenance Owner Operator can Perform ‹ Changing the Engine AIR Cleaner ‹ Coolant Change ‹ Changing Engine OIL‹ Spark Plugs Repair Parts Miscellaneous MaintenanceKW 150 KW Standby GAS Engine Driven Generator Sets Service ScheduleMaintenance Level 11-3 11-4 Problem Cause Correction Troubleshooting GuideStandby Generator Sets Standby Generator Sets Page PAN CB Conn BOX Page UL Circuit Breaker QJ-2P Page Assy STR 390 25AD1 CPL Page Components Included in 0G2283D Page Weldment Frame 2.4L C2 Page Battery Tray C1 CPL Page Gasket Bosch 32 Page Engine 2.4L Mitsubishi 4G64 Page Weldment Radiator Support 2.4L Page Flange Fuel Inlet Page Rear Wrap C2 CPL Page Exhaust Elbow 2 1/4 OD 2 1/2OD Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page C2 Units 04/07 a .Rev BackPg001

2.4L specifications

Generac Power Systems has established itself as a leading provider of energy solutions, and its 2.4L engine is a testimony to their commitment to innovation and reliability. This engine is designed for portable and standby generators, delivering exceptional performance and efficiency.

One of the standout features of the Generac 2.4L engine is its robust design, optimized for both heavy-duty use and demanding applications. The engineering focus ensures that the engine can withstand various environmental conditions while maintaining optimal operation. Additionally, its compact size makes it versatile for various generator models, making it a favored choice among manufacturers and users.

The 2.4L engine incorporates advanced technologies that enhance performance and fuel efficiency. One notable technology is the Electronic Fuel Injection (EFI) system. Unlike traditional carbureted engines, the EFI system provides precise fuel management, improving fuel efficiency and reducing emissions. This means users can expect longer run times on a single tank of fuel, a crucial advantage for those requiring power during outages or remote operation.

Furthermore, the Generac 2.4L engine is equipped with a state-of-the-art cooling system that maintains optimal operating temperatures even under heavy loads. This safeguard helps prevent overheating, thus extending the engine's longevity and reliability. The engine's low oil pressure shutdown feature adds another layer of protection by automatically shutting down the engine if oil pressure drops below a safe threshold.

Noise reduction is another priority for Generac, and the 2.4L engine reflects this commitment. With an integrated muffler and sound suppression features, the engine operates quietly without sacrificing power output. This is particularly beneficial for residential areas or environments where noise may be a concern.

In terms of maintenance, the Generac 2.4L engine requires minimal upkeep. Its design includes easily accessible components, allowing for straightforward maintenance routines. Regular oil changes and filter replacements ensure that the engine continues to perform at its best over time, providing users with peace of mind.

Overall, the Generac Power Systems 2.4L engine combines innovative features, advanced technologies, and reliable performance, making it an attractive choice for those in need of dependable power solutions. Whether for home backup or professional use, this engine exemplifies Generac's dedication to quality and user satisfaction.