Troubleshooting

My 12-Voltair not run

1.Check if the switch on the pressure switch is in the auto (down) position

2.Check the air pressure. If you have more than 120 PSI in the compressor, the compressor will not kick in and run until the pressure has dropped below 120 PSI

Before proceeding with this troubleshooting guide, be sure to disconnect the wire on the right

side of the solenoid. This is the wire that goes to the inside of the motor.

3.Do you have a toggle switch? If not skip to 4.

-Check if the toggle switch is in the on position

-Check your wiring against the wire diagram on previous page

-Check with a volt meter that you have voltage on at least one side of the switch (10-14 VDC) when the switch is in the off position

-Check to see if you have voltage on both sides of the switch when the switch is in the on position

4.Do you have a circuit breaker? If not skip to 5.

-Check to see if there is a reset on the circuit breaker

-Check to see if you have voltage on both sides of the circuit breaker (10-14 VDC)

5.Check to see if the solenoid is working

-Make sure the circuit breaker is engaged, the remote switch is on

-Make sure the switch is in the off position

-Put you hand on the top side of the solenoid with one hand and turn the switch on the pressure switch on with the other hand. You should feel a click. If not you possibly have a bad solenoid. Double check with the next step (Be sure the wire on the right side of the solenoid is disconnected)

-With a volt meter check the solenoid using the two different sceneries

Scenario

Left Post

Top Post

Right Post

Circuit breaker on

 

 

 

Remote Switch on

10-14 VDC

0 VDC

0 VDC

Pressure switch off

 

 

 

Circuit breaker on

 

 

 

Remote Switch on

10-14 VDC

10-14 VDC

10-14 VDC

Pressure switch on

 

 

 

DIAGNOSIS

-If you don’t get voltage on the top post in scenario #2 you have a bad pressure switch

-If you don’t get voltage of the right post in scenario #2 you have a bad solenoid

6.Was the compressor running and just quit?

-If the motor overheated (surface temp over 190F) than the thermal protector will have shut the system down until the temperature drops below 170F. This may take up to 30 minutes. WARNING: This is an automatic reset thermal protector- If all switches are on, and the thermal protector resets it will run without any warning. Never put hand in the box without first disconnecting the power.

“Air Where And When You Need It!”

®

 

Page 13

Page 13
Image 13
12Volt 12V6CF owner manual Troubleshooting, My 12-Voltair not run