7800 SERIES RELAY MODULES
Table 3. Hold and Fault Message Summary (continued).
Fault Code | System Failure |
| Recommended Troubleshooting |
|
|
|
|
Fault 18 | Flame sensed when shutter is | 1. | Check that flame is not present in the combustion chamber. |
*Flame Detected* | open and no flame is expected |
| Correct any errors. |
| during PREPURGE. | 2. | Make sure that the flame amplifier and flame detector are |
|
|
| compatible. |
|
| 3. | Check the wiring and correct any errors. Make sure F and G |
|
|
| wires are in individual conduits and protected from stray |
|
|
| noise pickup. |
|
| 4. | Remove the flame amplifier and inspect the connectors. |
|
|
| Reseat the flame amplifier. |
|
| 5. | Reset and sequence the relay module. |
|
| 6. | If the code reappears, replace the flame amplifier and/or the |
|
|
| flame detector. |
|
| 7. | If the fault persists, replace the relay module. |
|
|
|
|
Fault 19 | Flame was lost during MFEP or | 1. | Inspect the main fuel valve(s) and connection(s). |
*Main Flame Ign.* | the first 10 seconds of the RUN | 2. | Make sure that the fuel pressure is high enough to supply |
| state. |
| fuel to the combustion chamber. |
|
| 3. | Make sure the flame detector is positioned to obtain the |
|
|
| required flame signal strength; reset and recycle. |
|
|
|
|
Fault 20 | Low Fire Interlock switch failure | 1. | Check wiring and correct any errors. |
*Low Fire Sw. Off* | to close during PREPURGE. | 2. | Reset and sequence the relay module. |
|
| 3. | Use either the manual motor potentiometer to drive the |
|
|
| motor to the Low Fire position or use the Run/Test Switch |
|
|
| option, if available. Sequence to Prepurge drive to Low Fire |
|
|
| and place in the Test position. Adjust the Low Fire Switch |
|
|
| to make sure that it closes properly. |
|
| 4. | Measure the voltage between terminal 18 and G (ground) |
|
|
| while in the Prepurge drive to Low Fire state. Line supply |
|
|
| voltage should be present. If not, the switch adjustment is |
|
|
| incorrect and/or the switch is defective and needs |
|
|
| replacing. |
|
| 5. | Reset and sequence the relay module. If line supply voltage |
|
|
| was present between the Low Fire Switch and terminal 18, |
|
|
| and the fault still persists, replace the relay module. |
|
|
|
|
Fault 21 | Running Interlock fault during | 1. | Check wiring; correct any errors. |
*Running ILK* | PREPURGE. | 2. | Inspect the fan; make sure there is no blockage of the air |
|
|
| intake and that it is supplying air. |
|
| 3. | Make sure the Interlock Switches are working properly and |
|
|
| that all switch contacts are free of contaminants. |
Fault 22 | Lockout Interlock fault during | 4. | Reset and sequence the relay module to PREPURGE (place |
*Lockout ILK* | PREPURGE. |
| the Run/Test Switch in the Test position, if available). |
|
|
| Measure the voltage between terminals 7 and G (ground). |
|
|
| Line voltage should be present. |
Fault 23 | Combustion airflow interlock | 5. | If steps 1 through 4 are correct and the fault persists, |
*Airflow Switch* | fault during PREPURGE. |
| replace the relay module. |
|
|
|
|
Fault 24 | The flame interlock (relay | 1. | Check for F leadwire routing. Make sure routing is in its |
*Call Service* | module) was on when it should |
| conduit and isolated from |
| be off. |
|
|
Fault 25 | The flame interlock (relay |
|
|
*Call Service* | module) was off when it should |
|
|
| be on. |
|
|
|
|
|
|
Fault 26 | The Manual Open Valve Switch | 1. | Check wiring and correct any errors. |
was off when it should be on | 2. | Make sure that the Manual Open Valve Switch is fully open. | |
| (RM7838B only). | 3. | Make sure that the Manual Open Valve Switch is |
|
|
| functioning properly and that the switch contacts are free |
|
|
| from contaminants. |
|
| 4. | Reset and sequence the relay module. |
|
| 5. | Make sure that the Manual Open Valve Switch provides an |
|
|
| electrical path when closed. Verify that the relay module is |
|
|
| receiving power at terminal 17. |
|
| 6. | If steps 1 through 5 are correct and the fault persists, |
|
|
| replace the relay module. |
|
|
|
|
|
|
| (continued) |
12 |