5) Application example (II)
Target M1 = On, set 0x99>>Instance 1>>Attribute 2 of IFD9502 to “0004Hex”.
1> The connection
Note: IFD9502, a Delta DeviceNet slave module can connect the temperature controller to DeviceNet
network.
2> Compulsory settings and explanations on devices
Compulsory settings in DVPDNET-SL
Parameter Set value Explanation
Node address 00 Set the node address of DVPDNET-SL to “00”.
Set the communication speed of DVPDNET-SL and bus to
“500kbps”.
Baud rate 500kbps
Compulsory settings in DNA02
Parameter Set value Explanation
Node address 02 Set the node address of DNA02 to “02”.
Set the communication speed of DNA02 and bus to
“500kbps”.
Baud rate 500kbps
Compulsory settings in VFD-B
Parameter Set value Explanation
02-00 04 The main frequency is operated on RS-485 interface.
02-01 03
The operation commands are operated on the
communication interface. Operation by keys is valid.
09-00 01 Communication address of VFD-B: 01
09-01 03 Baud rate: 38,400
09-04 03 Modbus RTU mode. Data format <8, N, 2>
DVP-PLC Operation Manual 19