TROUBLESHOOTING
Please check guidelines below. For your safety, water heater service should be performed only by a qualified service technician. Read the GENERAL SAFETY INFORMATION section first.
PROBLEM | POSSIBLE MALFUNCTION | SERVICE TO BE PERFORMED |
| POSSIBLE SOLUTION | ||
NO HOT WATER | 1) | No pilot |
|
|
| |
|
| A. | No gas to pilot | Check gas supply |
| Turn on, check pressure |
|
|
|
| Check gas valve |
| Turn on or replace if needed |
|
|
|
| Check pilot orifice for obstruction |
| Clean with air or replace |
|
|
|
| Check pilot tube for kink or leaks |
| Replace pilot tube |
|
| B. | Pilot will not stay lit | Check gas pressure |
|
|
|
|
|
| Check thermostat MV |
|
|
|
|
|
| Check thermocouple connection and |
| Tighten if loose, replace |
|
|
|
| MV output |
| as necessary |
|
|
|
| Check thermocouple placement in pilot flame |
| 3/8- should be in flame |
|
|
|
| Check pilot for proper flame |
| Change pilot orifice |
|
|
|
| Check ECO operation |
| Replace gas valve |
|
|
|
| Check for air in pilot tube |
| Bleed as necessary |
|
| C. | Pilot blows out | Leaking joints |
| Check all vent joints for proper seal. |
|
|
|
|
|
| Make sure to check inner and outer |
|
|
|
|
|
| pipe and check rear air tube seals. |
|
|
|
|
|
| Refer to installation manual. |
|
|
|
| Check for proper vent cap |
| Install A. O. Smith provided vent cap |
|
|
|
| Check for bent, missing, or mislocated |
|
|
|
|
|
| pilot shield (natural gas units only) |
| Replace or reposition |
|
|
|
| Check outer door seal |
| Replace gasket if missing |
|
|
|
|
|
| Tighten screws if loose |
|
|
|
|
|
| Install gasket properly if misinstalled |
NOT ENOUGH | 1) | Incorrect burner orifice | Check orifice size |
| Replace with correct size | |
HOT WATER | 2) | No gas to main burner | Check gas supply |
| Correct as needed | |
|
|
|
| Check thermostat operation |
| Replace as needed |
| 3) | Heater too small | Confirm sizing requirements |
| Replace with larger heater, add | |
|
|
|
|
|
| another heater, or decrease |
|
|
|
|
|
| water usage. |
YELLOW FLAMES | 1) | Excessive or low gas | Check gas pressure |
|
| |
OR SOOT |
| pressure |
|
|
| |
| 2) | Combustion air restricted | Check vent for restrictions |
| Correct as necessary | |
|
|
|
| Check venting for extra piping |
| |
|
|
|
|
|
| the installation manual |
CONDENSATION | 1) | Water on floor under heater | See page 21 “CONDENSATION” |
|
| |
|
|
|
|
|
| |
BURNER WILL | 1) | Low gas pressure | Check gas supply pressure |
|
| |
NOT STAY LIT |
|
|
| Check thermostat operation |
|
|
| 2) | Downdraft or | Check for proper vent cap |
| Install proper vent cap | |
|
| backdraft condition | Check location of heater |
| ||
|
|
|
| Check for proper vent sealing |
| Reseal venting |
|
|
|
| Check top and/or bottom air supply |
| Seal as necessary |
|
|
|
| box for air leaks |
|
|
|
|
|
| Check outer door seal |
| Replace gasket, tighten screws |
|
|
|
|
|
| or |
|
|
|
|
|
|
|