1.11 Output Power Connectors
Depending on the fuse configuration used, the fuse platform will have at least one, and up to four, output power terminal blocks, located on the rear side of the platform. The number present will depend on the fuse type and number of fuse positions. In general, there will be one terminal block per bus for each fuse type present on that bus.
All of the output power terminal blocks are
Copper wire is used for output power wiring. Connections are typically made using ring or
Warning: In a fuse platform with KLM fuses, the
Table 1. Output Power Terminal Blocks
FUSE | FUSE HOLDER | TERMINAL | MAXIMUM | LUG/AWG | |
RANGE * | |||||
TYPE | MODULE | SCREW SIZE | TERMINAL WIDTH | ||
KLM | All sizes | 0.320 inch (8.128 mm) | #10 to #22 | ||
|
|
|
|
| |
TPA | All sizes | 0.320 inch (8.128 mm) | #10 to #22 | ||
|
|
|
|
| |
GMT | 4- or | 0.325 inch (8.255 mm) | #12 to #22 | ||
|
|
|
|
| |
GMT | 0.260 inch (6.604 mm) | #14 to #22 | |||
|
|
|
|
| |
TPA/GMT | 4 TPA fuses with | 0.320 inch (8.128 mm) | #10 to #22 | ||
| 10 GMT fuses | 0.200 inch (5.080 mm) |
| ||
| #16 to #24 | ||||
|
|
|
|
|
*Output terminal accepts wire sizes in the AWG range given; however, wire size should be determined based on local requirements and practice.
1.12Ground Connectors
Two #10 studs (with nuts) are provided for grounding the fuse platform chassis. The studs are mounted on 0.625 inch (15.875 mm) centers.
Two crimp ring lug terminals for two #10 AWG wires are provided with each fuse platform. The fuse platform may be grounded using only one stud.
1.13 Alarm Contact Operation
The fuse platform contains circuitry that opens and closes a set of alarm contacts when any fuse on the bus fails or when input power to the bus is lost. These contacts may be used to open or close a loop connected to an external alarm system.