ADCP-80-526 • Issue 6 • December 2006

4.Place the fuse platform in the specified mounting space within the rack.

5.Secure the fuse platform to the equipment rack as shown in Figure 14 using the four 3/8- inch (9.53 mm) long pan-head screws and flat washers provided.

Caution: Do not use any hardware other than the hardware supplied with the fuse platform.

TIGHTEN MOUNTING SCREWS TO 27 POUND-FORCE INCHES

(3.1 NEWTON METERS) OF TORQUE

DETAIL DRAWING OF

MOUNTING SCREWS

AND WASHERS

USE #12 STAR WASHERS INSTEAD OF FLAT

18865-A

WASHERS IF REQUIRED BY LOCAL PRACTICE

Figure 14. Mounting Fuse Platform on Rack

4.3Grounding Chassis

Use the following procedure to connect the panel to an approved office ground source:

1. Obtain two lengths of #10 AWG wire for use as the chassis grounding wires.

Note: A single ground wire can also be used. If using a single ground wire, use #6 AWG wire terminated at either stud.

2. Terminate one end of each wire with the #10 ring terminals provided (requires crimper).