4.Place the fuse platform in the specified mounting space within the rack.
5.Secure the fuse platform to the equipment rack as shown in Figure 14 using the four 3/8- inch (9.53 mm) long
Caution: Do not use any hardware other than the hardware supplied with the fuse platform.
TIGHTEN MOUNTING SCREWS TO 27
(3.1 NEWTON METERS) OF TORQUE
DETAIL DRAWING OF
MOUNTING SCREWS
AND WASHERS
USE #12 STAR WASHERS INSTEAD OF FLAT |
WASHERS IF REQUIRED BY LOCAL PRACTICE
Figure 14. Mounting Fuse Platform on Rack
4.3Grounding Chassis
Use the following procedure to connect the panel to an approved office ground source:
1. Obtain two lengths of #10 AWG wire for use as the chassis grounding wires.
Note: A single ground wire can also be used. If using a single ground wire, use #6 AWG wire terminated at either stud.
2. Terminate one end of each wire with the #10 ring terminals provided (requires crimper).