3.3Materials Required
The following materials are required to install the fuse platform:
•#2 AWG insulated copper wire for input power wires
•
•#10 AWG copper wire for ground connections
•Insulated copper wire for fused output power wires (refer to Table 1 on page 8)
•Ring or
•#16 to #30 AWG insulated copper wire for alarm terminal
•#22 to #26 AWG insulated copper wire for alarm terminal
•
3.4Continuity Tests
Each panel is thoroughly tested at the ADC factory before being shipped. However, before the panel is installed, continuity tests, as described here, should be performed to verify that no internal damage has occurred during shipping and handling.
Using a multimeter that is set to perform a continuity check, perform the following tests.
Test 1: Input Battery to Input
TEST 1- POWER BUS B: VERIFY NO CONTINUITY EXISTS BETWEEN BATT AND RTN TERMINALS
TEST 1- POWER BUS A: VERIFY NO CONTINUITY EXISTS BETWEEN BATT AND RTN TERMINALS
Figure 7. Test 1: Input Battery to Input Return
Test 2: Input Battery to Output
1.Remove the fuse holder from the fuse platform.
2.Insert a working fuse into the fuse holder.
Page 14
© 2006, ADC Telecommunications, Inc.