3.4

Technical Data

 

 

Type power

 

 

PROTECT C. 1000 (S)

1000 VA (cos ϕ = 0.7 lag.)

 

 

700 W

 

PROTECT C. 2000 (S)

2000 VA (cos ϕ = 0.7 lag.)

 

 

1400 W

 

PROTECT C. 3000 (S)

3000 VA (cos ϕ = 0.7 lag.)

 

 

2100 W

 

UPS Input (single phase)

 

 

 

 

 

Rated input voltage

220 / 230 / 240 Vac

 

Voltage tolerance range

160 Vac – 300 Vac ± 5 Vac

 

 

Bypass 80 Vac – 264 Vac

 

Nominal frequency

50 Hz / 60 Hz

 

 

(automatic detection)

 

Frequency tolerance range

± 4 Hz

 

Current consumption at full load (max.)

 

PROTECT C. 1000 (S)

7 A

 

PROTECT C. 2000

10 A

 

PROTECT C. 2000 S

12 A

 

PROTECT C. 3000 (S)

16 A

 

Input power factor

λ ￿ 0.96

 

Connection

Non-heating appliance

 

 

connector

 

Datalines

RJ11 (phone, fax, modem)

 

overvoltage protection

RJ45 (Ethernet 10/100MBit/s)

 

UPS Output (single phase)

 

 

Rated output voltage

220 / 230 / 240 Vac ±2 %

 

 

(configuration via software

 

 

“CompuWatch”)

 

Nominal frequency

50 Hz / 60 Hz ± 0,2 %

 

 

(depending on mains)

 

Voltage waveform

Harmonic distortion

 

 

￿ 4 % THD (linear load)

 

 

￿ 7 % THD (non-linear load)

14