Default setting: No automatic supply for load i over integrated bypass after executing step 1 and 2 (Modification of the configuration with the

provided Software ”CompuWatch“).

3.Then connect the outputs of your UPS to your loads. Use the load connection cables provided for this. Don’t switch on the loads yet. Please contact your dealer if you require additional load connection cables.

4.Now switch on the UPS. To do this, press and hold the UPS ON switch for about 2 seconds.

5.When being powered on, the UPS will perform self-diagnosis, the Load/Battery level LEDs will be turned on and then off one after another in ascending order. After synchronising the inverter successfully the LED “Inverter” will go on after some seconds, with the UPS in normal mode. If the power supply is in order (mains within the range) an additionally the LED “Line” will go on. If this LED is flashing, the phase and neutral of the

UPS are exchanged. In this case turn the mains connector 1800 in the shockproof socket.

i

Please shut down the entire system if you

cannot solve any problems which occur. Press

 

 

the OFF button for about 2 seconds. Disconnect

 

the UPS from the mains by pulling the mains

 

connector. Please contact our hotline (s.p. 4).

6.When all displays are lit as described, switch on your loads one after the other. Note the maximum permitted UPS load when doing this. Keep in mind that especially loads like laser printers and big CTRs have high power consumption and can cause an overload of the UPS quickly.

i

Behaviour when switching on / off:

The behaviour after switching on (On-

Pushbutton) or off (Off-Pushbutton) the UPS can

 

be defined with the Software “CompuWatch”:

 

Activation of the automatic bypass or either

 

deactivation (latter = factory-made presetting).

28