General data

Classification

VFI SS 211 acc. to IEC 62040–3

 

Double conversion technology

Overall efficiency AC-AC (full load)

PROTECT C. 1000 (S)

￿ 85 %

PROTECT C. 2000 (S)

￿ 85 %

PROTECT C. 3000 (S)

￿ 88 %

Noise level (1m distance)

PROTECT C. 1000 (S) PROTECT C. 2000 (S) PROTECT C. 3000 (S)

Type of cooling

<45 dB (A)

<50 dB (A)

<50 dB (A)

Forced cooling

by variable speed fans

Operating temperature range

0°C to +40°C

 

 

 

 

 

 

Recommendation +15°C to

 

 

+25°C (due to battery

 

 

 

 

system)

 

 

 

 

 

 

Storage temperature range

0°C to +40°C

 

 

 

 

Relative humidity

< 95%, non-condensing

 

 

Max. site altitude

up to 1000 m above sea level

 

 

If the UPS is installed or used

 

 

in a place where the altitude is

 

 

above than 1000m, the output

 

 

power has to be reduced:

 

 

 

 

 

 

 

 

 

 

 

 

Altitude (m)

 

1000

 

1500

 

2000

2500

3000

 

 

 

 

 

 

 

 

 

 

 

 

 

Derating Power

 

100%

 

95%

 

90%

85%

80%

 

 

 

 

 

 

 

 

 

 

 

 

Outlets

 

 

 

 

 

 

 

 

 

PROTECT C. 1000 (S)

4 x IEC 320-10A

 

 

 

PROTECT C. 2000 (S)

6 x IEC 320-10A

 

 

 

PROTECT C. 3000 (S)

4 x IEC 320-10A

 

 

 

 

 

+ 1 x IEC 320-16A

 

 

 

Equipment colour

Black line

 

 

 

 

17