Connection | |
| connectors |
Current Crest Ratio | 3:1 |
Overload behaviour | up to 105 % ± 5 % continuous; |
in battery mode | > 105 % ± 5 % – < 150 % ± 5 % |
| for 25 s; |
| 150 % ± 5 % for 200 ms |
Overload behaviour | up to 105 % ± 5 % continuous; |
with existing mains | > 105 % ± 5 % – < 150 % ± 5 % |
| for 30 s; |
| 150 % ± 5 % for 300 ms |
| Then automatic inverter to |
| Bypass in < 4 ms (switches |
| back when overload damps = |
| Load < 90%) |
Short circuit behaviour | 3 x IN for 140 ms |
Autonomy time (full load with internal battery)
PROTECT C. 1000 | 6 min |
PROTECT C. 2000 | 10 min |
PROTECT C. 3000 | 5 min |
Autonomy time with external optional battery expansions (only for PROTECT C. – models):
Coupled | Autonomy time (full load) |
|
| ||
|
|
|
|
| |
battery modules | C. 1000 |
| C. 2000 |
| C. 3000 |
|
| ||||
|
|
| |||
|
|
|
|
|
|
1 | 38 min |
| 55 min |
| 30 min |
2 | 76 min |
| 106 min |
| 60 min |
Rated direct voltage (intermediate circuit) |
|
| |||
PROTECT C. 1000 (S) |
| 36 V |
|
| |
PROTECT C. 2000 (S) |
| 96 V |
|
| |
PROTECT C. 3000 (S) |
| 96 V |
|
|
15