Connection

Non-heating appliance

 

connectors

Current Crest Ratio

3:1

Overload behaviour

up to 105 % ± 5 % continuous;

in battery mode

> 105 % ± 5 % – < 150 % ± 5 %

 

for 25 s;

 

150 % ± 5 % for 200 ms

Overload behaviour

up to 105 % ± 5 % continuous;

with existing mains

> 105 % ± 5 % – < 150 % ± 5 %

 

for 30 s;

 

150 % ± 5 % for 300 ms

 

Then automatic inverter to

 

Bypass in < 4 ms (switches

 

back when overload damps =

 

Load < 90%)

Short circuit behaviour

3 x IN for 140 ms

Battery

Autonomy time (full load with internal battery)

PROTECT C. 1000

6 min

PROTECT C. 2000

10 min

PROTECT C. 3000

5 min

Autonomy time with external optional battery expansions (only for PROTECT C. – models):

Coupled

Autonomy time (full load)

 

 

 

 

 

 

 

battery modules

C. 1000

 

C. 2000

 

C. 3000

 

 

 

 

 

 

 

 

 

 

 

1

38 min

 

55 min

 

30 min

2

76 min

 

106 min

 

60 min

Rated direct voltage (intermediate circuit)

 

 

PROTECT C. 1000 (S)

 

36 V

 

 

PROTECT C. 2000 (S)

 

96 V

 

 

PROTECT C. 3000 (S)

 

96 V

 

 