6.LED Line (Mains status): The green LED lights up if mains voltage is in a specified range of tolerance. The LED Line flashes when the phase and neutral conductor have been reversed at the input of the UPS system. In this case turn the mains connector 180° in the shockproof socket.

7.-11. LED Bargraph for UPS battery utilization resp. capacity (remaining autonomy time)

These LEDs show the load of the UPS system if the mains power is available (normal operation):

11. orange LED

96%

– 105%

10. green LED

76%

95%

9. green LED

56%

75%

8. green LED

36%

55%

7. green LED

0%

35%

In the battery operation, the LEDs indicate the capacity of the batteries:

11. orange LED

0%

25%

10. green LED

26%

50%

9. green LED

51%

75%

8. green LED

76%

95%

7. green LED

96%

– 100%

12.LED Fault: The red LED lights up and an acoustic warning signal is issued continuously when the UPS system is in fault condition.

36