6.2Fault Diagnosis / Fault Rectification
The PROTECT C. generates detailed error messages. Support personal can localise and interpret faults quickly and precisely.
6.2.1 | Error Messages |
|
|
|
|
|
|
| Problem | Cause | Solution |
|
|
|
|
| UPS does not start. | Mains and battery voltage | Check building wiring |
| No indication, no audible | not in the tolerance range, | socket outlet and input |
| signal even though system | possible battery deep | cable. |
| is connected to mains | discharge. |
|
| power supply. |
|
|
|
|
|
|
| LED “Line” flashes and | Phase and neutral | Rotate mains power |
| audible signal sounding | conductor at input of UPS | socket by 180° or |
| every 3 minutes. | system are reversed. | connect UPS system. |
|
|
|
|
| LED “Line” flashes and | Input power and/or | Check input power |
| LED “Battery” lights up. | frequency are out of | source (Voltage, |
|
| tolerance. | frequency) and inform |
|
|
| house electrician if |
|
|
| necessary. |
|
|
|
|
| LED “Line” and LED | Inverter not switched on. | Press |
| “Bypass” light up even |
| for about 2 seconds. |
| though the power supply |
|
|
| is available. No supply of |
|
|
| connected loads. |
|
|
|
|
|
|
| LED “Inverter” and LED | Mains power supply has | Try to replace mains |
| “Battery” lights up, and | failed. Automatic switch | supply (possibly |
| audible signal sounding | to battery mode. | triggered fuse in sub |
| every 4 seconds. |
| distribution). When |
|
|
| audible alarm sounding |
|
|
| every second, battery |
|
|
| is almost unloaded. At |
|
|
| this point it is time to |
|
|
| proceed with an system |
|
|
| shutdown of all you IT |
|
|
| equipment. |
|
|
|
|
| LED “fault” lights,audible | Overload of the UPS | Reduce utilizations of |
| signal once a second. | system. | UPS by removing loads |
|
|
| of UPS output. |
|
|
|
|