Wire colors
THREE 380 V + N + T
Black - black - brown ...….... Phases
Blue ..................................... | Neutral |
Green / yellow ..................... | Earth |
THREE 220 V + T |
|
Black - brown - blue ........... | Phases |
Green / yellow..................... | Earth |
Important:Install an additional upstream fuse cabinet.Furthermore, install a residual current operated circuit breaker (300 ma) for the general protection of your launderette against electrical faults.
These installations must be in accordance with valid regulations.Note: Fuses protect the control and power circuitry.Table: motor power
UHM027D UHM033D UHM049D UHM067D
Power in kW | 4 | 4 | 5.5 | 5.5 |
Nominal velocity in tr/min 1500 | 1500 | 1500 | 1500 |
Machines that have electrical heating have connections for:
•The control and motor circuits.
•The heating power circuit.
Table: heating power
UHM027D | UHM033D | UHM049D | UHM067D | ||||
230V | 400V | 230V | 400V | 230V | 400V | 230V | 400V |
Power in kW | 18 | 27 | 36 | 45 |
Inter combined AM | 50 32 | 80 50 | 100 60 | 100 60 |
Cable section MM2 | 4x10 5x6 | 4x10 5x6 | 4x16 5x6 | 4x16 5X10 |