Gas Requirements
Natural Gas and Liquefied Petroleum
WARNING
To reduce the risk of fire or explosion, DO NOT CONNECT THE GAS LINE TO THE TUMBLER IF THE GAS SERVICE IS NOT THE SAME AS THAT SPECIFIED ON THE TUMBLER SERIAL PLATE! It will first be necessary to convert the gas burner orifice and gas valve. Appropriate conversion kits are available.
W060
IMPORTANT: Any product revisions or conversions must be made by the Manufacturer’s Authorized Dealers, Distributors, or local service personnel.
IMPORTANT: The tumbler must be isolated from the gas supply piping system by closing its individual manual
34.5 mbar (0.5 psi).
IMPORTANT: The tumbler and its manually operated appliance gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 3.45 kPa, 34.5 mbar (0.5 psi).
IMPORTANT: The installation must comply with local codes.
WARNING
To reduce the risk of fire or explosion, if the tumbler is to be connected to Liquefied Petroleum (L.P.) gas, a vent to the outdoors must be provided in the room where the tumbler is installed.
W062
NOTE: This manual is only a supplement. Refer to installation/operation manual for full instructions.
Installation/Operation Supplement
European Gas
WARNING
To reduce the risk of electric shock, fire, explosion, serious injury or death:
•Disconnect electric power to the tumbler before servicing.
•Close gas shut-off valve to gas tumbler before servicing.
•Close steam valve to steam tumbler before servicing.
•Never start the tumbler with any guards/ panels removed.
•Whenever ground wires are removed during servicing, these ground wires must be reconnected to ensure that the tumbler is properly grounded.
W002
General Information
This information is to be used when installing gas tumblers in countries, and/or on gases, different than the machine’s factory configuration. Tumblers are supplied from the factory for operation on Natural Gas or L.P. Gas in the countries of GB/IE/PT/ES/IT/GR/ LU/CH. To install machines in any other country, or on any other gas, requires some level of modification.
Models are built in two different configurations:●Regulated Natural Gas – Burner orifice is sized for Natural Gas, second family, group H (E) at 20 mbar inlet pressure. Regulator/governor is operational. Gas valve CAN be
●Unregulated Liquefied Petroleum (L.P.) Gas – Burner orifice is sized for L.P., third family, group 3+ at 28.37 mbar inlet pressure. Regulator/ governor is blocked open. Gas valve CANNOT be
Serial plates supplied from the factory are configured for the countries of GB/IE/PT/ES/IT/GR/LU/CH. These instructions pertain to the situations when the country of use or gas supply is different than that on the serial plate.
NOTE: This manual is only a supplement. Refer to installation/operation manual for full instructions.
70392201 (EN) | © Published by permission of the copyright owner – DO NOT COPY or TRANSMIT | 15 |