WARNING
The washer-extractor should be connected to an individual branch
circuit not shared with lighting or other equipment.
Electrical Speciî‚¿cations HC60, IHC012, IHC06060 liters / 12 pounds
Boiler Fed/Steam Heat Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load Amps
Recommended Circuit
Breaker (US-market)
AWG/mm2
kW Standard
Heating Elements
Full Load Amps
Recommended
Circuit Breaker (US-
market)
AWG/mm2
US NON-US US NON-US
N 440-480 50/60 3 3+PE 3 10 10 14/2.5
3x2 kW
12 15 16 14/2.5
P 380-415 50/60 3 3+N+PE 7 15 16 14/2.5 16 20 20 12/4.0
Q200-240 50/60 3 3+PE 7 15 16 14/2.5 23 30 32 10/6.0
X 200-240 50/60 1/3 2/3+PE 7 15 16 14/2.5 N/A N/A N/A N/A
Alternative Electric Heat Options
N 440-480 50/60 3 3+PE
3x1.4 kW
N/A N/A N/A N/A
P 380-415 50/60 3 3+N+PE 13 15 16 14/2.5
Q200-240 50/60 3 3+PE 18 20 20 12/4.0
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
Table 2