WARNING
The washer-extractor should be connected to an individual branch
circuit not shared with lighting or other equipment.
Electrical Speciî‚¿cations HC75, IHC018, CHC018, IHC07575 liters / 18 pounds
Boiler Fed/Steam Heat Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load Amps
Recommended Circuit
Breaker (US-market)
AWG/mm2
kW Standard
Heating Elements
Full Load Amps
Recommended
Circuit Breaker (US-
market)
AWG/mm2
US NON-US US NON-US
N 440-480 50/60 3 3+PE 4 10 10 14/2.5
3x2 kW
13 15 16 14/2.5
P 380-415 50/60 3 3+N+PE 12 15 16 14/2.5 21 30 25 10/6.0
Q200-240 50/60 3 3+PE 12 15 16 14/2.5 27 30 32 10/6.0
X 200-240 50/60 1/3 2/3+PE 12 15 16 14/2.5 N/A N/A N/A N/A
Alternative Electric Heat Options
N 440-480 50/60 3 3+PE
3x1.4 kW
N/A N/A N/A N/A
P 380-415 50/60 3 3+N+PE 18 20 20 12/4.0
Q200-240 50/60 3 3+PE 23 30 25 10/6.0
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
N 440-480 50/60 3 3+PE
3x3 kW
N/A N/A N/A N/A
P 380-415 50/60 3 3+N+PE 25 30 32 10/6.0
Q200-240 50/60 3 3+PE 35 40 40 8/10.0
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
N 440-480 50/60 3 3+PE
3x4 kW
21 30 25 10/6.0
P 380-415 50/60 3 3+N+PE 29 40 32 8/10.0
Q200-240 50/60 3 3+PE N/A N/A N/A N/A
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
Table 4