4

WARNING

The washer-extractor should be connected to an individual branch circuit not shared with lighting or other equipment.

Electrical Specifications HF575, IHF575, IHF135, CHF135

575 liters / 135 pounds

 

 

 

 

 

Boiler Fed/Steam Heat

 

Electric Heat

 

Code

Voltage

Cycle

Phase

Wire

Full Load Amps

 

Recommended Circuit Breaker (US-market)

AWG/mm2

kW Standard Heating Elements

Full Load Amps

 

Recommended Circuit Breaker

AWG/mm2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

US

NON-US

 

 

 

US

NON-US

 

N

440-480

50/60

3

3+PE

27

30

32

10/6.0

9x4 kW

79

N/A

80

4/25

P

380-415

50/60

3

3+N+PE

27

30

32

10/6.0

79

N/A

80

4/25

 

Q

200-240

50/60

3

3+PE

52

60

60

8/10.0

9x3 kW

120

N/A

125

2/40

X

200-240

50/60

1/3

2/3+PE

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

Alternative Electric Heat Options

N

440-480

50/60

3

3+PE

 

 

 

 

 

66

N/A

70

4/25

P

380-415

50/60

3

3+N+PE

 

 

 

 

9x3 kW

66

N/A

70

4/25

Q

200-240

50/60

3

3+PE

 

 

 

 

79

N/A

80

4/25

 

 

 

 

 

X

200-240

50/60

1/3

2/3+PE

 

 

 

 

 

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

Table 3

 

 

 

 

 

 

31

Page 31
Image 31
Alliance Laundry Systems HF730, HF900, HF455 Electrical Specifications HF575, IHF575, IHF135, CHF135, Liters / 135 pounds