WARNING

The washer-extractor should be connected to an individual branch circuit not shared with lighting or other equipment.

Electrical Specifications HF730, IHF730, IHF165, CHF165

730 liters / 165 pounds

 

 

 

 

 

Boiler Fed/Steam Heat

 

Electric Heat

 

Code

Voltage

Cycle

Phase

Wire

Full Load Amps

 

Recommended Circuit Breaker (US-market)

AWG/mm2

kW Standard Heating Elements

Full Load Amps

 

Recommended Circuit Breaker

AWG/mm2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

US

NON-US

 

 

 

US

NON-US

 

N

440-480

50/60

3

3+PE

44

50

50

8/10.0

9x4 kW

96

N/A

100

2/40

P

380-415

50/60

3

3+N+PE

44

50

50

8/10.0

96

N/A

100

2/40

 

Q

200-240

50/60

3

3+PE

85

90

90

4/25.0

 

153

N/A

180

4/0 /

9x3 kW

100

 

 

 

 

 

 

 

 

 

 

 

 

X

200-240

50/60

1/3

2/3+PE

N/A

N/A

N/A

N/A

 

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

Alternative Electric Heat Options

N

440-480

50/60

3

3+PE

 

 

 

 

 

83

N/A

90

2/40

P

380-415

50/60

3

3+N+PE

 

 

 

 

 

83

N/A

90

2/40

Q

200-240

50/60

3

3+PE

 

 

 

 

9x3 kW

153

N/A

180

4/0 /

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

X

200-240

50/60

1/3

2/3+PE

 

 

 

 

 

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

Table 4

 

 

 

 

 

 

32

Page 32
Image 32
Alliance Laundry Systems HF900, HF575, HF455 Electrical Specifications HF730, IHF730, IHF165, CHF165, Liters / 165 pounds