4
30
WARNING
The washer-extractor should be connected to an individual branch
circuit not shared with lighting or other equipment.
Electrical Speciî‚¿cations HF455, IHF455, IHF100, CHF100455 liters / 100 pounds
Boiler Fed/Steam Heat Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load Amps
Recommended Circuit
Breaker (US-market)
AWG/mm2
kW Standard
Heating Elements
Full Load Amps
Recommended
Circuit Breaker
AWG/mm2
US NON-US US NON-US
N 440-480 50/60 3 3+PE 22 30 32 10/6.0 9x4 kW 74 N/A 80 4/25
P 380-415 50/60 3 3+N+PE 22 30 32 10/6.0 74 N/A 80 4/25
Q200-240 50/60 3 3+PE 36 40 40 8/10.0 9x3 kW 104 N/A 125 2/40
X200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A N/A N/A N/A N/A
Alternative Electric Heat Options
N 440-480 50/60 3 3+PE
9x3 kW
61 N/A 70 4/25
P 380-415 50/60 3 3+N+PE 61 N/A 70 4/25
Q200-240 50/60 3 3+PE 104 N/A 125 2/40
X200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
Table 2