Electrical Requirements . . .

(Electric Dryers)

NOTE: The wiring diagram is located inside the control hood.

WARNING

To reduce the risk of fire, electric shock, serious injury or death, all wiring and grounding MUST conform with the latest edition of the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1, and such local regulations as might apply. It is the customer’s responsibility to have the wiring and fuses checked by a qualified electrician to make sure your home has adequate electrical power to operate the dryer.

W113

Grounding Instructions

This dryer must be connected to a grounded metal, permanent wiring system; or an equipment-grounding conductor must be run with the circuit conductors and connected to the equipment-grounding terminal or lead on the dryer.

NOTE: The power cord (pigtail) is NOT supplied with the electric dryer. Type of pigtail and gauge of wire must conform to local codes and instructions.

POWER SUPPLY

POWER SUPPLY

3-WIRE GROUNDED NEUTRAL

120/240 VOLT, 60 HERTZ AC 1 PHASE SERVICE ENTRANCE SWITCH BOX (SEE NOTE BELOW)

The method of wiring the dryer is optional and subject to local

 

 

 

code requirements.

 

 

30 AMPERE FUSES OR

 

 

 

 

CIRCUIT BREAKER

 

NOTE: Connect the dryer to the power supply with the

NEUTRAL WIRE

NEUTRAL WIRE

 

MAXIMUM RATED VOLTAGE listed on the nameplate.

 

 

A typical

INTERMEDIATE

 

 

 

 

30-Amp

 

 

 

 

FUSE BOX

 

 

INTERMEDIATE

 

Three-wire

 

 

 

(MAY BE

METALLIC OR

SHUT-OFF BOX

 

Receptacle

 

OMITTED IF

 

NEMA Type

NON-METALLIC

(MAY OR MAY

 

SERVICE

 

10-30R

SHEATHED CABLE

NOT BE FUSED)

 

ENTRANCE

 

 

(COPPER WIRE

 

 

 

BOX IS FUSED)

 

 

 

ONLY)

 

 

 

 

 

 

 

 

 

WALL

 

 

 

 

 

RECEPTACLE

PIGTAIL

 

 

 

 

 

 

 

 

 

 

TO DRYER

 

 

 

120 ± 12

 

(SEE NOTE BELOW)

 

 

120 ± 12

VAC

 

 

 

NEUTRAL

VAC

 

 

 

 

 

 

 

 

 

240 ± 12

 

NEUTRAL

TERMINAL BLOCK

 

 

 

IN DRYER

 

VAC

 

 

 

 

 

 

 

 

NOTE: Use COPPER WIRE only. Shorter than 15' (4.5 m) use 10 A.W.G. Longer than 15' (4.5 m) use 8 A.W.G.

L1

L2

L1

L2

PIGTAIL CONNECTION

DIRECT CONNECTION

D003IE3A

A typical 30-Amp

Four-wire Receptacle

 

120 ± 12

120 ± 12

VAC

VAC

 

 

240 ± 12

 

VAC

120 ± 12

120 ± 12VAC

VACD006IE1F

12