Venting

Venting

A 4 inch diameter flue transition is factory installed on the combustion air inducer outlet of all models. Figure 16 shows the combustion air inducer as shipped from the factory.

Mounting Screws Location

Figure 15

UPFLOW POSITION

Top Vent Discharge

Figure 16

Mounting Screws LocationUPFLOW POSITION IMPORTANT

The unit will not vent properly with the flue transition pointed down in the 6 o’clock position.

The combustion air inducer may be rotated clockwise or counterclockwise by 90° to allow for top or side vent discharge in all applications. When the unit is installed, the flue transition must be in the 9 o’clock, 12 o’clock or 3 o’clock position.

If necessary reposition the combustion air inducer, pressure switch and/or make-up box as needed per the following steps. See Figures 16 through 22.

1.Remove the four mounting screws (Figure 15) which secure the combustion air inducer / pressure switch assembly to the orifice plate. Lift the assembly and rotate it 90° clockwise or counter clockwise to either the 3 o’clock position. Resecure with four secrews. Gasket should be left in place.

2.Use tin snips to cut preferred opening on the cabinet for repositioning the flue outlet. Use the cut-out piece as a cover plate to patch unused opening on cabinet.

UPFLOW POSITION

Left Side Vent Discharge

Remove make-up box assembly (2 screws) and cut wire tie to free make- up box wires. Re install make-up box on other side of cabinet.

Resecure make-up box wires: Either pull excess wires through the blower companrtment and secure using supplied wire tie, or coil excess wire and secure to the gas manifold.

Figure 17

UPFLOW POSITION

Right Side Vent Discharge

Pressure switch tubing may be too long. Cut to fit, then reattach to barbed fitting on pressure switch. Tubing must not be allowed to sag.

Figure 18

506526-01

Issue 1031

Page 13 of 39

Page 13
Image 13
Allied Air Enterprises 80G1UH, A80UH Venting, Mounting Screws Location Figure UPFLOW POSITION, Upflow Position