9.Remove screws from both sides, top and bottom of vestibule panel.
10.Remove heat exchanger. It may be necessary to spread cabinet side to allow more room. If so, remove five screws from the left side or right side of cabinet. See Figure 40.
11.Backwash using steam. Begin from the bumer opening on each clam. Steam must not exceed 275°F.
12.To clean burners, run a vacuum cleaner with a soft brush attachment over the face of burners. Visually inspect inside the burners and crossovers for any blockage caused by foreign matter. Remove any blockage. Figure 38 shows burner detail.
13.To clean the combustion air inducer visually inspect and using a wire brush clean where necessary. Use compressed air to clean off debris and any rust.
14.Reinstall heat exchanger in vestibule. (Replace the five screws in the cabinet from step 10 if removed).
15.NOx units only - Replace NOx inserts.
16.Reinstall collector box and combustion air assembly. Reinstall all screws to the collector box and combustion air inducer. Failure to replace all screws may cause leaks. Inspect gaskets for any damage and replace if necessary.
17.Reinstall burner box, manifold assembly and burner box cover.
Remove 5 Screws If Necessary
(either side of cabinet)
NOx INSERTS
Figure 39
Figure 40
18.Reconnect all wires.
19.Reconnect top cap and vent pipe to combustion air inducer outlet.
20.Reconnect gas supply piping.
21.Turn on power and gas supply to unit.
22.Set thermostat and check for proper operation.
23.Check all piping connections, factory and field, for gas leaks. Use a leak detecting solution or other preferred means.
CAUTION
Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use matches, candles, flame or other sources of ignition to check for gas leaks.
24.If a leak is detected, shut gas and electricity off and repair leak.
25.Repeat steps 24 and 26 until no leaks are detected.
26.Replace access panel.
Issue 1031 | Page 35 of 39 |