Cleaning the Heat Exchanger and Burners

Cleaning the Heat Exchanger and Burners

NOTE: Use papers or protective covering in front of the furnace during cleaning.

1.Turn off both electrical and gas power supplies to furnace.

2.Remove flue pipe and top cap (some applications top cap can remain) from the unit.

3.Label the wires from gas valve, rollout switches, primary limit switch and make-up box then disconnect them.

4.Remove the screws that secure the combustion air inducer/pressure switch assembly to the collector box. Carefully remove the combustion air inducer to avoid damaging blower gasket. If gasket is damaged, it must be replaced to prevent leakage.

5.Remove the collector box located behind the combustion air inducer. Be careful with the collector box gasket. If the gasket is damaged, it must be replaced to prevent leakage.

6.Disconnect gas supply piping. Remove the screw securing the burner box cover and remove cover. Remove the four screws securing the burner manifold assembly to the vestibule panel and remove the assembly from the unit.

7.Remove screws securing burner box and remove burner box.

8.NOX units only - Remove screw securing NOX insert. Remove NOX insert. See Figure 39.

BURNER, COMBUSTION AIR INDUCER ASSEMBLY & HEAT EXCHANGER REMOVAL