Allied Air Enterprises Upflow specifications Figure VENT EXIT OPTIONS, To Convert toSide Flue Exit

Models: Downflow or Horizontal 2 Stage Heat Variable Speed Gas Fired Non-Condensing Warm Air Furnace Upflow

1 28
Download 28 pages 32.15 Kb
Page 14
Image 14
Figure 9

4.All pipe should be supported using the proper clamps and/or straps. These supports should be at least every four (4') feet.

5.All horizontal runs of pipe should have at least a 1/4" (in.) per foot of upward slope from the furnace to the vent terminal.

6.All runs of pipe should be as short as possible with as few turns as possible.

7.Seams should be tightly joined and checked for leaks.

8.The flue pipe must not extend into the chimney but be flush with the inside wall.

9.The chimney or vent pipe must extend at least three (3') feet above the highest point where it passes through a roof of a building and at least two (2') feet higher than any portion of a building within a horizontal distance of ten (10') feet. It shall also extend at least five (5') feet above highest connected equipment flue collar.

Figure 9

VENT EXIT OPTIONS

10.The 3" to 4" vent adaptor coupling must be used to connect to the combustion blower outlet. It must be installed directly to the combustion blower outlet (See Figure 8).

To Convert to Side Flue Exit:

1.Remove the louver door from the furnace. (Be sure the side vent exit knock-out is removed from the right side panel of the cabinet. See Figure 9.)

2.Disconnect the pressure switch tubing from the combustion blower.

3.Remove the four (4) screws that secure the combustion blower adaptor plate to the flue collector box, taking care to support the blower assembly so that it does not fall.

4.Rotate the blower 90° (degrees) clockwise, so that the outlet of the blower is pointing toward the right side panel of the furnace.

5.Insure that the gasket is in place between the blower adaptor plate and the flue collector box. Reattach the blower assembly to the flue collector box, using the four (4) screws removed in step 3. Be sure that the screws are properly tightened and that the gasket seals the plate to the box.

6.Reconnect the pressure switch tubing to the combustion blower.

7.(Optional) Install vent pipe guard. Kit Number 20284801.

Figure 10

VENT PIPE GUARD KIT

For Horizontal Positions:

It is not necessary to reposition any of the components of the furnace in order to install it in either horizontal position. As outlined above, it is permissible to use the side vent exit for the horizontal-left position, if desired.

Checking For Vent Oversizing:

If this furnace is replacing a furnace that is attached to a venting system serving other appliances, the venting system is likely to be too large to properly vent all of the attached appliances. An improperly sized venting system can lead to condensation, leakage, or spillage.

20571201

Issue 0527

Page 14 of 28

Page 14
Image 14
Allied Air Enterprises Upflow Figure VENT EXIT OPTIONS, To Convert toSide Flue Exit, Figure VENT PIPE GUARD KIT