ADE-120ES (72 Kw Electric) Reversing, 3ø

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES: A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.

B.Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.

C.Circuit breakers for 3Ø dryers must be 3-pole type.

OVEN SIZE

SERVICE

 

WIRE

APPROX.

MINIMUM

FUSING

CIRCUIT

PHASE

AMP DRAW

Dual Element

((Kw)

VOLTAGE

SERVICE

WIRE SIZE*

BREAKER

 

60 Hz

50 Hz

Time Delay

 

 

 

 

 

 

72

208

3

214

---

4/0

300

300

72

240

3

186

187

3/0

250

250

72

380

3

117

117

1

150

150

72

380

4

117

117

1

150

150

72

416

3

---

107

2

150

150

72

416

4

---

107

2

150

150

72

480

3

98

---

3

150

125

72

480

4

98

---

3

150

125

72

575/600

3/4

79.4

---

4

100

110

 

 

 

 

 

 

 

 

 

*AWG Stranded Type Wire ... for individual lengths less than 100 feet. (Motor lead type wire is recommended)

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the back of the dryer, at the upper right hand corner. In the case of 208 VAC or 240 VAC, the supply voltage must match the electric service specifications of the data label exactly.

WARNING: 208 VAC and 240 Volts ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time, without notice or obligation.