24
*AWG Stranded Type Wire ... for individual lengths less than 100 feet.
(Motor lead type wire is recommended)

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is

affixed to the back of the dryer, at the upper right hand corner. In the case of

208 VAC or 240 VAC, the supply voltage must match the electric service

specifications of the data label exactly.

WARNING: 208 VAC and 240 Volts ARE NOT THE SAME. Any damage done to dryer

components due to improper voltage connections will automatically VOID THE

WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time, without notice or

obligation.

ADE-120ES (80 Kw Electric) Reversing, 3ø
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME . When ordering, specify exact voltage.
NOTES:A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to
appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3Ø dryers must be 3-pole type.
OVEN SIZE
((Kw) SERVICE
VOLTAGE PHASE WIRE
SERVICE
APPROX.
AMP DRAW MINIMUM
WIRE SIZE*
FUSING CIRCUIT
BREAKER
Dual Element
Time Delay60 Hz 50 Hz
80 208 3ø 3235 --- 250 MCM 300 300
80 240 3ø 3206 208 4/0 300 300
80 380 3ø 3--- 130 1 175 175
80 380 3ø 4--- 130 1 175 175
80 416 3ø 3--- 119 1 150 150
80 416 3ø 4--- 119 1 150 150
80 480 3ø 3188 --- 2 150 150
80 480 3ø 4108 --- 2 150 150
80 575 3ø 3/4 88 --- 3 125 125
80 600 3ø 3/4 85 --- 3 125 125