2.Electrical Service Specifications
MLG-200 (Gas)
7.5 Hp Blower/3 Hp Drive Motor
ELECTRIC SERVICE SPECIFICATION (PER DRYER)
IMPORTANT: 208 VAC and 230 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A. Fuse ratings are dual
B.Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to appliance amp draw rating and type of breaker used.
C.Circuit breakers for 3Ø dryers must be
SERVICE |
| WIRE | APPROX. | MINIMUM | FUSING | CIRCUIT | ||
PHASE | AMP DRAW | WIRE | Dual Element | |||||
VOLTAGE | SERVICE | BREAKER | ||||||
| 60 Hz | 50 Hz | SIZE* | Time Delay | ||||
|
|
|
| |||||
|
|
|
|
|
|
|
| |
208 | 3Ø | 3/4 | 37 | 4 | 60 | 80 | ||
|
|
|
|
|
|
|
| |
230 | 3Ø | 3 | 36 | 4 | 60 | 80 | ||
|
|
|
|
|
|
|
| |
380 | 3Ø | 3/4 | 20 | 8 | 30 | 40 | ||
|
|
|
|
|
|
|
| |
416 | 3Ø | 3/4 | 19 | 8 | 30 | 40 | ||
|
|
|
|
|
|
|
| |
460 | 3Ø | 3/4 | 18 | 8 | 30 | 40 | ||
|
|
|
|
|
|
|
|
* AWG Stranded Type Wire...for individual lengths less than 100 feet (30.48 meters).
WARNING: 208 VAC and 230 VAC ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.
IMPORTANT: The dryer must be connected to the electrical supply shown on the data label that
is affixed to the back of the dryer, at the upper right hand corner. In case of 208 VAC or 230 VAC, the supply voltage must match the electric service specifications of the data label exactly.