4.Front PanelBLUE” Light and “RED” Light “ON”

ADS-464 “ON” button does respond ...

a.PROBABLE CAUSES;

1a) EMERGENCY STOP (E-STOP) BUTTONS 1, 2, and 3.

b.POSSIBLE SOLUTIONS;

1b) Verify that ALL EMERGENCY STOP (E-Stop) buttons are pushed in.

EMERGENCY STOP 1 - main enclosed door

EMERGENCY STOP 2 - pendent control

EMERGENCY STOP 3 - rear control panel (2-door models only)

If ALL EMERGENCY STOP (E-Stop) buttons are “disengaged,” press “ON” located on the main enclosure door.

If “NO,” go to section 3 on page 47

Does the system “GREEN” “ON” light illuminate?

If not, check the EMERGENCY STOP (E-Stop) and drying system “ON/OFF” circuits. (Refer to ladder diagram.)

5.Front PanelBLUE” (main panel) light, “RED” (sprinkler power) light, and “GREEN” (control power) light “ON

The system has one or more of the following symptoms;

• OPERATOR INTERFACE TERMINAL - no display or displays “LINE FAULT” message

• PROGRAMMABLE LOGIC CONTROLLER (PLC) - no indicator lights “ON”

• CONVENIENCE OUTLET - no power

HI-LIMIT CONTROLLERS (HLS1 and HLS2) - no display

a.PROBABLE CAUSES;

1a) Fuse 7 -- PLC (Programmable Logic Controller) power Fuse 8 -- 24 volt DC power

Fuse 9 -- convenience outlet Fuse 10 - hi-limit controller power

2a) Malfunctioning PLC (Programmable Logic Controller).