2.WIRING BACK TO THE PLC (Programmable Logic Controller), 0, 8

a)PROBABLE CAUSES;

1.CLOGGED LINT SCREEN OR LINT BAG

2.AIR PRESSURE SETTING

3.AIR PRESSURE SWITCH - PS3 OR WIRING BACK TO THE PLC (Programmable Logic Controller)

b)POSSIBLE SOLUTIONS;

1.Perform preventive maintenance and screen cleaning procedures.

2.Set correct pressure settings.

3.For a quick check of the AIR PRESSURE SWITCH WIRING, perform the following:

-Run a drying cycle

-Does the pressure switch’s indicator come “ON”?

-If “YES,” switch and its adjustment

-If “NO,” check switch and its adjustment

-Verify that PLC (Programmable Logic Controller) input L.E.D. #5 comes “ON”

-Does L.E.D. #5 come “ON” when the switch is active?

-If “YES,” wiring is OK

-If “NO,” check:

-Switch, its setting and wiring

-Check wiring back to the base electrical junction box

-Check PLC (Programmable Logic Controller)

-Refer to blueprints: Main Electrical Panel Diagram, Base Junction Box Wiring Diagram

-Re-test; verify that the signal is operational