TUMBLER FORWARD “PENDANT” --- PB1

This push button comprises of one normally open switch, and is mechanically interlock with Tumbler Reverse Push Button.

EMERGENCY STOP (E-STOP) “PENDANT” --- PB6

This push button switch is normally open device and its function is to shut down the control voltage to the dryer in the event it is pressed.

NOTE: It WILL NOT effect the sprinkler circuit power.

2.0Verify Pendant Electrical Signals

ALL the pendant control signals are interfaced to the Main Electrical Panel’s PLC (Programmable Logic Controller) except for “Emergency Stop.”

Load - Level - Unload Switch ----- A and B

Tumbler Reverse Switch ----------- PB2

Tumbler Forward Switch ----------- PB1

Emergency Stop (E-Stop) Switch - PB6

For a quick check of the wiring of SEL 1 and 2 to the PLC (Programmable Logic Controller) perform the following test with the control voltage “ON”. (Green Button)

Turn the selector switch to LOAD

Does PLC (Programmable Logic Controller) input L.E.D. #15 light?

Turn the selector switch to UNLOAD

Does PLC (Programmable Logic Controller) input #16 light?

Turn the selector switch to LEVEL

Are both PLC (Programmable Logic Controller) input #15 and input #16 “OFF”?

If the answers to these questions are “YES,” wiring to the PLC (Programmable Logic Controller) is correct

If any answer to these questions is “NO,” refer to Probable Causes paragraph on page 74 and page 75

Tumbler Reverse Switch --- PB2

For a quick check of the wiring of PB2 to the PLC perform the following test with control voltage “ON” (“GREEN” button)

Press the REVERSE Push-button.

Does PLC (Programmable Logic Controller) input L.E.D. #18 light?