Alarms and Events

 

Alarms

Description

Action

 

 

 

 

46.

Communication to parallel IF

UPS fault

Call for assistance

 

lost

 

 

 

 

 

 

47.

External shutdown accepted

Remote signal for switching off

 

 

UPS accepted.

 

 

 

UPS switches off automatically

 

 

 

 

 

48.

Communication to VQ mains

UPS fault

Call for assistance

 

lost

 

 

 

 

 

 

49.

Bypass syncronization error

The UPS cannot synchronize with

Check if phase rotation of bypass

 

 

bypass utility

voltage is correct – if OK, call for

 

 

 

assistance

 

 

 

 

50.

Battery charge error

Transferred to battery operation

Check RFI input fuse and

 

 

because of battery charge error

feedback relay

 

 

 

 

5.4Rectifying Alarm Messages

Following actions may rectify alarm:

Check local utility supply. Fuses may be blown or supply switched off accidentally

Check if UPS cooling air intake is blocked

Check if load exceeds maximum output capacity

If, with power switched on, there is no UPS output voltage - and an attempt to restart the UPS is in vain - use the external service bypass switch to bypass UPS.

1.“Battery weak” message appears: Reset “battery weak” signal according to section 4.0 Parameter Settings and initiate battery capacity test according to section 6.3 Battery Capacity Test. Make a record of obtained back-up time and use battery monitor to reset alarm. Leave the UPS to recharge battery for at least 16 hours. Start up second battery test without changing the load. If the test result shows improved back-up time, continue the test series until no or just insignificant improvements are obtainable. If battery is still weak - call for assistance.

2.“Battery Defective” message appears: Call for assistance. See section 8 “How to contact APC”.

5.5Parallel Operation Alarms

The parallel operation alarm message is: Communication to parallel IF lost

In the event of a parallel operation alarm, all parallel operation functions controlled by Advanced Power Management will be inactive. In such situations only simple hardware control such as load-sharing, operation mode etc. is possible.

Correction of false alarm situations during service:

When one system is isolated for service, the above alarm message will apppear if two systems still operating. To delete this alarm message re-program the station addresses on all systems in the following sequence:

1 to max_number_system

990-4039

User Guide APC Silcon 240-320kW 480V UPS

27

Page 27
Image 27
American Power Conversion 240-320kW 480V manual Rectifying Alarm Messages, Parallel Operation Alarms