Stop/Start UPS and Operating the External Service Bypass

2.6.2Switching the Parallel System from External Bypass into Normal UPS Operation

Single Utility

Utility

Dual Utility

H003

Load Utility 2

Load

Service bypass switch

APC Silcon

UPS

APC Silcon

UPS

 

 

Q003

 

 

Service

 

 

bypass

 

 

switch

 

H010a

 

Utility 1

Q010a

APC Silcon

 

UPS

 

Q001a

 

 

 

H010b

 

 

Q010b

APC Silcon

 

Q001b

UPS

 

 

Q004

H002a

Q002a

H002b

Q002b

H004

NOTICE!

If battery has been disconnected, please refer to section 2.4.1 UPS start-up.

 

990-4039

 

 

14

User Guide APC Silcon 240-320kW 480V UPS

Page 14
Image 14
American Power Conversion 240-320kW 480V manual Stop/Start UPS and Operating the External Service Bypass