Stop/Start UPS and Operating the External Service Bypass

2.7Isolating one UPS in a Parallel Configuration for Service/Maintenance

2.7.1 Isolating one UPS in a Parallel/Redundant System

Single Utility

Utility

Dual Utility

H003

Load Utility 2

Load

Service bypass switch

APC Silcon

UPS

APC Silcon

UPS

 

 

Q003

 

 

Service

 

 

bypass

 

 

switch

 

H010a

 

Utility 1

Q010a

APC Silcon

UPS

 

Q001a

 

 

 

H010b

 

 

Q010b

APC Silcon

 

Q001b

UPS

 

 

Q004

H002a

Q002a

H002b

Q002b

H004

In a redundant system one UPS may be isolated for service/maintenance without affecting other parallel UPS(S).

Action

1.Check that the remaining UPS(s) will be able to carry the load when one UPS is isolated.

2.Switch off the system to be isolated for maintenence by pushing the red OFF button.

3.Disconnect output and utility by setting output switches (Q002) to position 0 and input switch (Q001) to position 0. Disconnect battery by opening battery breaker.

4.If system has dual utility, set the bypass input switch (Q010) to position 0.

2.7.2Switching Back the UPS to Normal Parallel/Redundant Operation

Action

1.Set the input switch (Q001) and the output switch (Q002) to position 1.

2.If system has dual utility, set the bypass input switch (Q010) to position 1.

3.Charge capacitors, connect battery and start up the UPS as described in 2.4.1. Start UPS (from complete power down).

The UPS will automatically switch to normal operation and start load-sharing with the other parallel UPS(s).

 