Operation
3.2Display of Measured Values
To read measurements, press one or two keys simultaneously as shown in table below. (Illustrated values are examples only).
NOTICE!
Please note mains = utility
Action | Display shows |
98.01.16 System off 10.22,13
Mains 1 voltage 480 480 480Vac
Mains 1 current 100 100 100Aac
Mains 2 voltage 480 480 480Aac
Mains 2 current 100 100 100Aac
Battery voltage
System off 438 437Vdc
Battery current
+ 20Adc
Output voltage 480 480 480Vac
Output current 180 180 180Aac
Output frequency
60Hz
Battery temperature
25°C
Output peak current
255 255 255 A
Normal operation load power xx%
Batt. load : 0
Batt. tank: 100
Description
Year, month, day
Hour, minute, second
Utility 1 voltage is 3 x 480V
Utility 1 curent is 3 x 100A
Utility 2 voltage is 3 x 480V
Utility 2 current is 3 x 100A
Battery voltage is 438Vdc on battery 1 438 437Vdc on battery 2
Charging current is (+) 20Adc (Discharging current (⎟))
Output voltage is 3 x 480V
Output current is 3 x 180A
Output frequency is 60Hz
Battery temperature is 25°C (77°F)
Output peak current is 3 x 255A
Returns to normal status indication. If not pressed, automatic switch back will be performed after 20 seconds
Battery load in percent.
Left battery capacity in percent
| |
|
|
User Guide APC Silcon | 19 |