Storage

Storage

Storage Conditions

Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS for at least two hours. Remove any accessories in the accessory slot and disconnect any cables connected to the computer interface port to avoid unnecessarily draining the battery.

Extended storage

At -15 to +30 °C (+5 to +86 °F), charge the UPS’s battery every six months.

At +30 to +45 °C (+86 to +113 °F), charge the UPS’s battery every three months.

Replacing the Battery

This UPS has an easy to replace hot-swappable battery. Battery replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and loads on for the following procedure. See your dealer or call the number listed under APC Contact Information, page 19, for information on replacement battery cartridges.

Note:

Please read the cautions in the Safety section at the beginning of this User’s Manual.

Once the battery is disconnected, the loads are not protected from power outages.

Model Number

Replacement Battery Cartridge (RBC) #

SU1400XLTNET

RBC 11

 

 

SU2200XLTNET

RBC 11

 

 

SU3000TNET

RBC 11

 

 

SU5000T

RBC 12

 

 

SU1400RMXLTNET

RBC 11

 

 

SU2200RMXLTNET

RBC 11

 

 

SU3000RMT3U

RBC 12

 

 

SU5000RMT5U

RBC 12

 

 

11

990-7031C, Revision 4 12/99