American Power Conversion 2200XLT User Configuration Items, How to Determine On-Battery Run Time

Models: 1400XLT 5000T 2200XLT 3000T

1 30
Download 30 pages 62.88 Kb
Page 21
Image 21
User Configuration Items

User Configuration Items

Note: Setting these items requires optional software or hardware.

Function

Factory Default

User Selectable Choices

Description

Automatic Self-Test

Every 14 days

Every 7 days (168 hours), On

Sets the interval at which the UPS will execute a self-test.

 

(336 hours)

Startup Only, No Self-Test

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight characters to define

Use this field to uniquely identify the UPS for network

 

 

the UPS.

management purposes.

 

 

 

 

Date of Last Battery Replacement

Manufacture Date

Date of Battery Replacement

Reset this date on battery replacement.

Minimum Capacity Before Return from

0 percent

15, 50, 90 percent

The UPS will charge its batteries to the specified percentage

Shutdown

 

 

before return from a shutdown.

 

 

 

 

Sensitivity

Normal

Reduced, Low

Set lower than normal sensitivity to avoid lowered battery

 

 

 

capacity and service life in situations where the load can

 

 

 

tolerate minor power disturbances.

 

 

 

 

Duration of Low Battery Warning

2 minutes

5, 7, 10 minutes

Sets the time before shutdown at which the UPS issues a low

 

 

 

battery warning. Set higher than the default only if the OS

 

 

 

needs the time for graceful shutdown.

 

 

 

 

Alarm Delay After Line Fail

5 second delay

30 second delay, At Low Battery

To avoid alarms for minor power glitches, set the alarm delay.

 

 

Condition, No Alarm

 

 

 

 

 

Shutdown Delay

20 seconds

180, 300, 600 seconds

Sets the interval between when the UPS receives a shutdown

 

 

 

command and when shutdown occurs.

 

 

 

 

Synchronized Turn-on Delay

0 seconds

60, 180, 300 seconds

To avoid branch circuit overload, the UPS will wait the

 

 

 

specified time after the return of utility power before turn-on.

 

 

 

 

High Transfer Point

229

224, 234, 239

To avoid unnecessary battery usage, set the High Transfer

 

 

 

Point higher if the utility voltage is chronically high and the

 

 

 

load is known to work well under this condition.

 

 

 

 

Low Transfer Point

177

168, 172, 182

Set the Low Transfer Point lower if the utility voltage is

 

 

 

chronically low and the load can tolerate this condition.

 

 

 

 

How to Determine On-Battery Run Time

Note:

UPS battery life differs based on usage and environment.

APC recommends that the battery/batteries be changed once every two years.

Tower and 5U Models - 1400VA and 2200VA Models

Typical On-Battery Runtime Versus Load, in Hours

 

 

1

2

3

4

5

6

7

8

9

10

Load

Internal

Battery

Battery

Battery

Battery

Battery

Battery

Battery

Battery

Battery

Battery

(VA)

Battery

Pack

Packs

Packs

Packs

Packs

Packs

Packs

Packs

Packs

Packs

100

4.50

9.75

15.42

21.08

26.75

32.42

38.08

43.75

49.41

55.08

60.75

200

2.75

6.25

9.75

13.50

17.25

21.08

24.83

28.58

32.33

36.17

39.92

300

1.83

4.50

7.08

9.67

12.50

15.33

18.08

20.92

23.75

26.58

29.42

400

1.33

3.42

5.42

7.50

9.58

11.83

14.08

16.33

18.58

20.75

23.00

500

1.05

2.67

4.42

6.08

7.83

9.50

11.33

13.25

15.08

16.92

18.75

600

0.85

2.17

3.67

5.08

6.50

8.00

9.42

11.00

12.58

14.17

15.75

700

0.68

1.75

3.00

4.25

5.50

6.75

8.00

9.26

10.67

12.00

13.33

800

0.58

1.50

2.58

3.75

4.83

5.92

7.08

8.17

9.25

10.50

11.67

900

0.48

1.27

2.25

3.25

4.25

5.25

6.25

7.25

8.25

9.17

10.25

1000

0.43

1.12

2.00

2.83

3.75

4.67

5.58

6.42

7.33

8.25

9.17

1200

0.33

0.88

1.52

2.25

3.00

3.75

4.50

5.25

6.00

6.75

7.50

1400

0.27

0.70

1.22

1.83

2.50

3.08

3.75

4.42

5.00

5.67

6.25

1600

0.22

0.57

1.00

1.47

2.00

2.58

3.08

3.67

4.17

4.75

5.25

1800

0.18

0.48

0.87

1.25

1.75

2.17

2.67

3.17

3.67

4.17

4.67

2000

0.15

0.42

0.73

1.08

1.45

1.92

2.33

2.75

3.17

3.67

4.08

2200

0.13

0.35

0.63

0.93

1.25

1.67

2.00

2.42

2.83

3.17

3.58

15