American Power Conversion 3000T Tower and 5U Rack Mount Models - 3000 & 5000 VA Models, Load

Models: 1400XLT 5000T 2200XLT 3000T

1 30
Download 30 pages 62.88 Kb
Page 22
Image 22

Tower and 5U Rack Mount Models - 3000 & 5000 VA Models

 

 

 

Typical On-Battery Run Time Versus Load, in Hours

 

Load

3000 VA Internal Battery

 

3000 VA w/ 1 Battery Pack

5000 VA Internal Battery

 

100 VA

3.80

 

 

8.18

 

7.17

 

150 VA

3.05

 

 

6.57

 

5.95

 

200 VA

2.35

 

 

5.42

 

5.04

 

300 VA

1.83

 

 

4.08

 

3.88

 

400 VA

1.40

 

 

3.22

 

2.96

 

500 VA

1.12

 

 

2.62

 

2.37

 

600 VA

0.90

 

 

2.18

 

1.92

 

800 VA

0.58

 

 

1.6

 

1.40

 

1000 VA

0.43

 

 

1.22

 

1.06

 

1200 VA

0.33

 

 

0.97

 

0.83

 

1400 VA

0.27

 

 

0.70

 

0.65

 

1600 VA

0.22

 

 

0.58

 

0.54

 

2000 VA

0.17

 

 

0.42

 

0.39

 

2200 VA

0.13

 

 

0.37

 

0.33

 

2500 VA

0.11

 

 

0.30

 

0.26

 

3000 VA

0.08

 

 

0.22

 

0.19

 

3500 VA

-

 

 

-

 

0.16

 

4000 VA

-

 

 

-

 

0.13

 

4500 VA

-

 

 

-

 

0.11

 

5000 VA

-

 

 

-

 

0.09

3U Rack Mount Models - 2200 & 3000 VA Models

 

 

 

 

 

 

 

 

 

 

 

 

 

Typical On-Battery Run Time Versus Load, in Hours

 

 

 

 

Load

 

NS2200RM

NS3000RM

 

 

 

 

 

 

SU2200RM

SU3000RM

 

 

 

 

 

 

 

(3U)

(3U)

 

 

 

 

50 VA

 

5.60

4.53

 

 

 

 

75 VA

 

4.73

3.93

 

 

 

 

100 VA

 

4.08

3.45

 

 

 

 

150 VA

 

3.15

2.75

 

 

 

 

200 VA

 

2.53

2.25

 

 

 

 

250 VA

 

2.10

1.88

 

 

 

 

300 VA

 

1.77

1.60

 

 

 

 

350 VA

 

1.52

1.40

 

 

 

 

400 VA

 

1.32

1.23

 

 

 

 

450 VA

 

1.16

1.08

 

 

 

 

500 VA

 

1.03

0.97

 

 

 

 

550 VA

 

0.92

0.87

 

 

 

 

600 VA

 

0.83

0.78

 

 

 

 

700 VA

 

0.67

0.63

 

 

 

 

800 VA

 

0.54

0.55

 

 

 

 

900 VA

 

0.50

0.48

 

 

 

 

1000 VA

 

0.45

0.43

 

 

 

 

1200 VA

 

0.35

0.33

 

 

 

 

1400 VA

 

0.28

0.27

 

 

 

 

1600 VA

 

0.23

0.22

 

 

 

 

2000 VA

 

0.15

0.15

 

 

 

 

2200 VA

 

0.13

0.13

 

 

 

 

2500 VA

 

-

0.10

 

 

 

 

3000 VA

 

-

0.06

 

990-7031C, Revision 4 12/99

16

Page 22
Image 22
American Power Conversion 3000T, 5000T Tower and 5U Rack Mount Models - 3000 & 5000 VA Models, Load, VA Internal Battery