Configuration
UPS settings
Settings are adjusted through PowerChute software or optional SmartSlot accessory cards.
Function | Factory | User Selectable | Description | |
Default | Choices | |||
|
|
|
| |
Automatic | On startup and | • On startup and every | Set the interval at which the UPS will execute a | |
every 14 days | 7 days (168 hours) | |||
| (336 hours) | there after |
|
|
| there after | • On startup and every |
| |
|
| 14 days (336 hours) |
| |
|
| there after |
|
|
|
| • On startup only |
| |
|
| • No |
|
|
|
|
|
| |
UPS ID | UPS_IDEN | Up to eight characters | Uniquely identify the UPS, (i.e. server name or | |
|
| (alphanumeric) | location) for network management purposes. | |
|
|
|
|
|
Date of Last | Manufacture | mm/dd/yy |
| Reset this date when you replace the battery |
Battery | Date |
|
| module. |
Replacement |
|
|
|
|
|
|
|
|
|
Minimum Capacity | 0 percent | • 0% | • 60% | Specify the percentage to which batteries will |
Before Return from |
| • 15% | • 75% | be charged following a low battery shutdown |
Shutdown |
| • 30% | • 90% | before powering connected equipment. |
|
| • 45% |
|
|
|
|
|
|
|
Voltage Sensitivity | High sensitivity | Brightly |
| Adjust by pressing the VOLTAGE SENSITIVIY |
The UPS detects |
| illuminated: high | switch (rear panel). Use a pointed object, (such | |
| sensitivity | as a pen) to do so. | ||
and reacts to line |
| |||
voltage distortions |
| Dimly illuminated: | Note: In situations of poor power quality, the | |
by transferring to |
| medium sensitivity | UPS may frequently transfer to battery | |
battery operation to |
| No illumination: | operation. If the connected equipment can | |
protect the |
| operate normally under such conditions, reduce | ||
| low sensitivity | |||
connected |
| the sensitivity setting to conserve battery | ||
|
|
| ||
equipment. |
|
|
| capacity and service life. |
|
|
|
|
|
Alarm Delay | Enable | • Enable |
| Mute ongoing alarms or disable all alarms. |
Control |
| • Mute |
|
|
|
| • Disable |
|
|
|
|
|
|
|
Shutdown Delay | 90 seconds | • 0 s | • 360 s | Set the interval between the time when the UPS |
|
| • 90 s | • 450 s | receives a shutdown command and actual |
|
| • 180 s | • 540 s | shutdown. |
|
| • 270 s | • 630 s |
|
|
|
|
|
|
12 |