Configuration

UPS settings

Settings are adjusted through PowerChute software or optional SmartSlot accessory cards.

Function

Factory

User Selectable

Description

Default

Choices

 

 

 

 

Automatic

On startup and

• On startup and every

Set the interval at which the UPS will execute a

Self-Test

every 14 days

7 days (168 hours)

self-test.

 

(336 hours)

there after

 

 

 

there after

• On startup and every

 

 

 

14 days (336 hours)

 

 

 

there after

 

 

 

 

• On startup only

 

 

 

• No self-test

 

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight characters

Uniquely identify the UPS, (i.e. server name or

 

 

(alphanumeric)

location) for network management purposes.

 

 

 

 

 

Date of Last

Manufacture

mm/dd/yy

 

Reset this date when you replace the battery

Battery

Date

 

 

module.

Replacement

 

 

 

 

 

 

 

 

 

Minimum Capacity

0 percent

• 0%

• 60%

Specify the percentage to which batteries will

Before Return from

 

• 15%

• 75%

be charged following a low battery shutdown

Shutdown

 

• 30%

• 90%

before powering connected equipment.

 

 

• 45%

 

 

 

 

 

 

 

Voltage Sensitivity

High sensitivity

Brightly

 

Adjust by pressing the VOLTAGE SENSITIVIY

The UPS detects

 

illuminated: high

switch (rear panel). Use a pointed object, (such

 

sensitivity

as a pen) to do so.

and reacts to line

 

voltage distortions

 

Dimly illuminated:

Note: In situations of poor power quality, the

by transferring to

 

medium sensitivity

UPS may frequently transfer to battery

battery operation to

 

No illumination:

operation. If the connected equipment can

protect the

 

operate normally under such conditions, reduce

 

low sensitivity

connected

 

the sensitivity setting to conserve battery

 

 

 

equipment.

 

 

 

capacity and service life.

 

 

 

 

 

Alarm Delay

Enable

• Enable

 

Mute ongoing alarms or disable all alarms.

Control

 

• Mute

 

 

 

 

• Disable

 

 

 

 

 

 

 

Shutdown Delay

90 seconds

• 0 s

• 360 s

Set the interval between the time when the UPS

 

 

• 90 s

• 450 s

receives a shutdown command and actual

 

 

• 180 s

• 540 s

shutdown.

 

 

• 270 s

• 630 s

 

 

 

 

 

 

12

Smart-UPS 5000 VA 208/230 Vac Tower/Rack-Mount 5U User Manual

Page 16
Image 16
American Power Conversion 5000VA user manual UPS settings, Function Factory User Selectable Description Default Choices