American Power Conversion 5000VA 5U, 208VAC user manual The UPS is overloaded

Models: 5000VA 5U 208VAC

1 14
Download 14 pages 5.64 Kb
Page 12
Image 12

PROBLEM AND POSSIBLE

SOLUTION

CAUSE

 

THE OVERLOAD LED IS ILLUMINATED AND THE UPS EMITS A SUSTAINED ALARM TONE

The UPS is overloaded.

The connected equipment exceeds the specified “maximum load” as defined in

 

Specifications at the APC web site, www.apc.com.

 

The alarm remains on until the overload is removed. Disconnect nonessential equip-

 

ment from the UPS to eliminate the overload.

 

The UPS continues to supply power as long as it is online and the circuit breaker

 

does not trip; the UPS will not provide power from batteries in the event of a utility

 

voltage interruption.

 

If a continuous overload occurs while the UPS is on battery, the unit turns off output

 

in order to protect the UPS from possible damage.

 

 

THE REPLACE BATTERY LED IS ILLUMINATED

Replace Battery LED flashes and

Check that the battery connectors are fully engaged.

short beep is emitted every two

 

seconds to indicate the battery is

 

disconnected.

 

Weak battery.

Allow the battery to recharge for 24 hours. Then, perform a self-test. If the problem

 

persists after recharging, replace the battery.

Failure of a battery self-test.

The UPS emits short beeps for one minute and the replace battery LED illuminates.

 

The UPS repeats the alarm every five hours. Perform the self-test procedure after the

 

battery has charged for 24 hours to confirm the replace battery condition. The alarm

 

stops and the LED clears if the battery passes the self-test.

 

 

THE INPUT CIRCUIT BREAKER TRIPS (208V MODELS ONLY)

The toggle handle on the circuit

Reduce the load on the UPS by unplugging equipment and resetting the toggle han-

breaker (located to the right of the

dle to ON.

input cable connection) switches

 

off.

 

 

 

AVR BOOST OR AVR TRIM LEDS ILLUMINATE

Your system is experiencing exces-

Have qualified service personnel check your facility for electrical problems. If the

sive periods of low or high voltage.

problem continues, contact the utility company for further assistance.

 

 

UPS OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTS

UPS input circuit breaker tripped.

Reduce the load on the UPS by unplugging equipment and resetting the circuit

 

breaker (on the back of UPS) by pressing the plunger in.

Very high, low, or distorted line

Move the UPS to a different outlet on a different circuit. Test the input voltage with

voltage. Inexpensive fuel powered

the utility voltage display (see below). If acceptable to the connected equipment,

generators can distort the voltage.

reduce the UPS sensitivity.

 

 

BATTERY CHARGE AND BATTERY LOAD LEDS FLASH SIMULTANEOUSLY

The internal temperature of the UPS

Check that the room temperature is within the specified limits for operation.

has exceeded the allowable thresh-

Check that the UPS is properly installed allowing for adequate ventilation.

old for safe operation.

 

 

Allow the UPS to cool down. Restart the UPS. If the problem continues contact

 

APC at, www.apc.com/supoport.

 

 

10

Page 12
Image 12
American Power Conversion 5000VA 5U, 208VAC user manual The UPS is overloaded