3:USER CONFIGURABLE ITEMS

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT

ACCESSORY CARDS.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

 

Automatic Self-Test

Every 14 days

Every 7 days

This function sets the interval

 

(336 hours)

(168 hours),

 

at which the UPS will execute

 

 

On Startup Only, No

a self-test. Refer to your soft-

 

 

Self-Test

 

ware manual for details.

 

 

 

 

UPS ID

UPS_IDEN

Up to eight characters to

Use this field to uniquely

 

 

define the UPS

identify the UPS, (ie. server

 

 

 

 

name or location) for network

 

 

 

 

management purposes.

 

 

 

 

Date of Last Battery Re-

Manufacture

Date of Battery Replace-

Reset this date when you

placement

Date

ment

 

replace the battery module.

 

 

mm/dd/yy

 

 

 

 

 

 

 

Minimum Capacity Before

0 percent

15, 50, 90 percent

The UPS will charge its bat-

Return from Shutdown

 

 

 

teries to the specified percent-

 

 

 

 

age.

 

 

 

 

 

Voltage Sensitivity

 

Brightly lit: UPS is set to

To change the UPS sensitiv-

The UPS detects and reacts

 

high sensitivity (default).

ity, press the voltage sensitiv-

 

 

 

ity button

(rear panel).

to line voltage distortions

 

Dimly lit:

UPS is set to

 

Use a pointed object (such as

by transferring to battery

 

medium sensitivity.

 

a pen) to do so.

operation to protect the

 

Off:

Low battery

 

 

 

connected equipment.

 

You can change the sensitiv-

Where power quality is

 

warning interval is about

ity level through PowerChute

poor, the UPS may fre-

 

eight minutes.

software.

 

quently transfer to battery

 

 

 

 

 

operation. If the connected

 

 

 

 

 

equipment can operate

 

 

 

 

 

normally under such condi-

 

 

 

 

 

tions, reduce the sensitivity

 

 

 

 

 

setting to conserve battery

 

 

 

 

 

capacity and service life.

 

 

 

 

 

 

 

 

 

Alarm Delay

5 second delay

30 second delay,

Set alarm delay to avoid

After Line Fail

 

At Low Battery

alarms for minor power

 

 

Condition,

 

glitches.

 

 

 

No Alarm

 

 

 

 

 

 

 

Shutdown Delay

20 seconds

180, 300, 600 seconds

Sets the interval between the

 

 

 

 

time when the UPS receives a

 

 

 

 

shutdown command and ac-

 

 

 

 

tual shutdown.

 

 

 

 

 

 

 

 