2:OPERATION

INDICATORS AND CONTROLS ON THE SMART-UPS

SMART-UPS FRONT PANEL

Power On

Power Off

Load

Battery Charge

Online

The online LED illuminates when the UPS is supplying utility power to the

 

connected equipment.

AVR Trim

AVR Boost

On Battery

Overload

Replace Battery

Battery Disconnected

This LED illuminates to indicate the UPS is compensating for a high utility voltage.

This LED illuminates to indicate the UPS is compensating for a low utility voltage.

When the on battery power LED is illuminated the UPS is supplying battery power to the connected equipment.

The LED illuminates and the UPS emits a sustained alarm tone when an over- load condition occurs.

Failure of a battery self-test causes the UPS to emit short beeps for one minute and the replace battery LED illuminates. Refer to Troubleshooting in this man- ual.

The replace battery LED flashes and short beep is emitted every two seconds.

4

Page 6
Image 6
American Power Conversion 5000VA 5U, 208VAC user manual Operation