American Power Conversion 208VAC, 5000VA 5U voltage sensitivity button, 230V models, 208V models

Models: 5000VA 5U 208VAC

1 14
Download 14 pages 5.64 Kb
Page 9
Image 9
voltage sensitivity button

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT

ACCESSORY CARDS.

FUNCTION

FACTORY

USER SELECTABLE

 

DESCRIPTION

DEFAULT

 

 

CHOICES

 

 

 

 

 

 

Low Battery Warning.

 

 

 

Brightly lit: Low battery

The low battery warning

 

2 min.

 

PowerChute interface

 

 

warning interval is about

beeps are continuous when

 

 

 

 

 

 

two minutes.

less than 7 minutes of run

 

 

 

software provides auto-

 

 

 

 

 

 

Dimly lit: Low battery

time remain.

matic, unattended shut-

 

 

 

 

 

 

warning interval is about

To change the warning inter-

down when approximately

 

 

 

 

 

 

five minutes.

two minutes (by default) of

 

 

 

val default setting, press the

 

 

 

Off: Low battery warning

battery operated run time

 

 

 

voltage sensitivity button

 

 

 

interval is about seven

remains.

 

 

 

while pressing and holding

 

 

 

minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the

button.

 

 

 

 

 

 

2 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 min.

 

 

 

 

 

 

 

 

 

 

7 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Synchronized Turn-on

0 seconds

60, 180, 300 seconds

The UPS will wait the speci-

Delay

 

 

 

 

 

 

 

 

fied time after the return of

 

 

 

 

 

 

 

 

 

utility power before turn-on

 

 

 

 

 

 

 

 

 

(to avoid branch circuit over-

 

 

 

 

 

 

 

 

 

load).

 

 

 

 

 

 

 

 

 

 

 

High Transfer Point

230V models:

230V models:

To avoid unnecessary battery

 

253VAC

264, 271, 280VAC

usage, set the high transfer

 

208V models:

208V models:

point higher if the utility volt-

 

age is chronically high and

 

229VAC

234, 239, 224VAC

 

the connected equipment is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

known to work under this

 

 

 

 

 

 

 

 

 

condition.

 

 

 

 

 

 

 

 

 

 

Low Transfer Point

230V models:

230V models:

Set the low transfer point

 

196VAC

188, 204, 208VAC

lower if the utility voltage is

 

208V models:

208V models:

chronically low and the con-

 

nected equipment can tolerate

 

177VAC

182, 168, 172VAC

 

this condition.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7