American Power Conversion 7500/10000 VA user manual Models

Models: 7500/10000 VA

1 21
Download 21 pages 7.94 Kb
Page 12
Image 12

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, WEB/SNMP CARD, OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

High Bypass Point

+10% of

+5%, +10%, +15%,

Maximum voltage that the UPS

 

output voltage

+20%

will pass to connected

 

setting

 

equipment during internal

 

 

 

bypass operation.

 

 

 

 

Low Bypass Point

-30% of output

-15%, -20%, -25%, -30%

Minimum voltage that the UPS

 

voltage setting

 

will pass to connected

 

 

 

equipment during internal

 

 

 

bypass operation.

 

 

 

 

Output Voltage

200 V models:

200 V models:

Allows the user to select the

 

200 VAC

200VAC

UPS output voltage while

 

208 V models:

208 V models:

online.

 

208 VAC

200, 208, 220, 230, 240

 

 

220V models:

VAC

 

 

220 VAC

220V models:

 

 

230 V models:

200, 208, 230, 240 VAC

 

 

230 VAC

230 V models:

 

 

 

200, 208, 220, 230, 240

 

 

 

VAC

 

 

 

*Use the voltage setting

 

 

 

applicable to your region.

 

 

 

 

 

Output Frequency

Automatic

50 ± 3 Hz,

Sets the allowable UPS output

 

(50 ± 3 Hz or

50 ± 0.1 Hz,

frequency. Whenever possible,

 

60 ± 3 Hz,

the output frequency tracks the

 

60 ± 3 Hz)

 

60 ± 0.1 Hz

input frequency.

 

 

 

 

 

 

Number of Battery

1

Number of Connected

Defines the number of

Packs

 

Batteries (four battery

connected battery packs for

 

 

modules per pack)

proper runtime prediction.

 

 

 

 

10