Hardwiring
Attention: Wiring must be performed by a qualified electrician.
1.Install a utility circuit breaker in accordance with local electrical codes (see tables below) for input wiring only.
2.Switch the UPS input circuit breaker (see A) and utility circuit breakers OFF.
3.Remove the access panel (see B).
4.Remove circular knockouts.
5.Run wires through access panel to terminal blocks. Wire to ground block first. Adhere to all national and local electrical codes. (See tables and graphics.)
6.Use appropriate glands to achieve
XLT, XLJ, AND XLTW MODELS
Input Connection |
|
|
|
|
|
| Output Connection (optional) |
|
| ||||
Wire to L1, L2, and . |
|
|
|
| Wire to L1A, L2A, and | . |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
System |
| Wiring |
|
| Voltage | Current | External Input |
| Wire Size | ||||
|
|
|
|
|
|
|
| Full Load | Circuit Breaker |
| (typical) | ||
|
|
|
|
|
|
|
| (Nominal) | (typical) |
|
|
| |
SURT7500XLJ, |
| Input & Output |
| 200/208/220V | 40 amps | 50 amps / |
| #8AWG/ | |||||
SURT7500XLT, |
|
|
|
|
|
| XLTW- 38 amps | Input Wiring Only |
| 10mm2 | |||
SURT7500XLTW |
|
|
|
|
|
|
|
|
|
|
|
| |
SURT10000XLJ, |
| Input & Output |
| 200/208/220V | 54 amps | 70 amps / |
| #6AWG/ | |||||
SURT10000XLT, |
|
|
|
|
|
| Input Wiring only |
| 16mm2 | ||||
SURT10000XLTW |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
XLI MODELS |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| ||
Input Connections |
|
|
|
|
|
| Output Connection (optional) |
|
| ||||
|
|
|
|
|
|
|
|
|
| ||||
|
| Wire to L1A, N1, and | . |
|
|
| |||||||
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| |||
System |
| Wiring | Number |
| Voltage | Current |
| External Input |
| Wire Size | |||
|
|
|
| of |
|
| Full Load |
| Circuit Breaker |
| (typical) | ||
|
|
|
| Phases |
|
| (Nominal) |
| (typical) |
|
| ||
SURT7500XLI |
| Input | 1 |
|
| 220/230/240V | 38 amps |
| 50 amps / |
| 10mm2 | ||
|
|
|
|
|
|
|
|
|
|
| |||
|
| Input | 3+ |
|
| 380/400/415V | 14 amps / phase when | 50 amps / |
| 10mm2 | |||
|
|
|
| Neutral |
|
| online, 38 amps on L1 |
|
|
|
| ||
|
|
|
|
|
|
|
| in bypass |
|
|
|
|
|
|
| Output | 1 |
|
| 220/230/240V | 38 amps |
| (not required) |
| 10mm2 | ||
|
|
|
|
|
|
|
|
|
|
|
| ||
SURT10000XLI |
| Input | 1 |
|
| 220/230/240V | 50 amps |
| 63 amps / |
| 16mm2 | ||
|
| Input | 3+ |
|
| 380/400/415V | 18 amps / phase when | 63 amps / |
| 16mm2 | |||
|
|
|
| Neutral |
|
| online, 50 amps on L1 |
|
|
|
| ||
|
|
|
|
|
|
|
| in bypass |
|
|
|
|
|
|
| Output | 1 |
|
| 220/230/240V | 50 amps |
| (not required) |
| 16mm2 |
2