American Power Conversion 7500/10000 VA user manual Hardwiring, XLT, XLJ, and Xltw Models

Models: 7500/10000 VA

1 21
Download 21 pages 7.94 Kb
Page 4
Image 4

Hardwiring

Attention: Wiring must be performed by a qualified electrician.

1.Install a utility circuit breaker in accordance with local electrical codes (see tables below) for input wiring only.

2.Switch the UPS input circuit breaker (see A) and utility circuit breakers OFF.

3.Remove the access panel (see B).

4.Remove circular knockouts.

5.Run wires through access panel to terminal blocks. Wire to ground block first. Adhere to all national and local electrical codes. (See tables and graphics.)

6.Use appropriate glands to achieve strain-relief on the hardwired input and output power cables.

XLT, XLJ, AND XLTW MODELS

Input Connection

 

 

 

 

 

 

Output Connection (optional)

 

 

Wire to L1, L2, and .

 

 

 

 

Wire to L1A, L2A, and

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

 

Wiring

 

 

Voltage

Current

External Input

 

Wire Size

 

 

 

 

 

 

 

 

Full Load

Circuit Breaker

 

(typical)

 

 

 

 

 

 

 

 

(Nominal)

(typical)

 

 

 

SURT7500XLJ,

 

Input & Output

 

200/208/220V

40 amps

50 amps / 2-pole for

 

#8AWG/

SURT7500XLT,

 

 

 

 

 

 

XLTW- 38 amps

Input Wiring Only

 

10mm2

SURT7500XLTW

 

 

 

 

 

 

 

 

 

 

 

 

SURT10000XLJ,

 

Input & Output

 

200/208/220V

54 amps

70 amps / 2-pole for

 

#6AWG/

SURT10000XLT,

 

 

 

 

 

 

XLTW-50 amps

Input Wiring only

 

16mm2

SURT10000XLTW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XLI MODELS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Connections

 

 

 

 

 

 

Output Connection (optional)

 

 

 

 

 

 

 

 

 

 

 

 

Single-Phase: Wire to L1, N, and .

 

 

Wire to L1A, N1, and

.

 

 

 

Three-Phase: Wire to L1, L2, L3, N, and .

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

 

Wiring

Number

 

Voltage

Current

 

External Input

 

Wire Size

 

 

 

 

of

 

 

Full Load

 

Circuit Breaker

 

(typical)

 

 

 

 

Phases

 

 

(Nominal)

 

(typical)

 

 

SURT7500XLI

 

Input

1

 

 

220/230/240V

38 amps

 

50 amps / 2-pole

 

10mm2

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

3+

 

 

380/400/415V

14 amps / phase when

50 amps / 4-pole

 

10mm2

 

 

 

 

Neutral

 

 

online, 38 amps on L1

 

 

 

 

 

 

 

 

 

 

 

 

in bypass

 

 

 

 

 

 

 

Output

1

 

 

220/230/240V

38 amps

 

(not required)

 

10mm2

 

 

 

 

 

 

 

 

 

 

 

 

SURT10000XLI

 

Input

1

 

 

220/230/240V

50 amps

 

63 amps / 2-pole

 

16mm2

 

 

Input

3+

 

 

380/400/415V

18 amps / phase when

63 amps / 4-pole

 

16mm2

 

 

 

 

Neutral

 

 

online, 50 amps on L1

 

 

 

 

 

 

 

 

 

 

 

 

in bypass

 

 

 

 

 

 

 

Output

1

 

 

220/230/240V

50 amps

 

(not required)

 

16mm2

2

Page 4
Image 4
American Power Conversion 7500/10000 VA user manual Hardwiring, XLT, XLJ, and Xltw Models